INA-HLN-080A1-DC

RHP · 8000 m³/h
InAir · RHP Heat-Pump Energy Recovery AHU (Sensible & Latent)
INA-HLN-080A1-DC
Heat-Pump Energy Recovery AHU (Sensible & Latent) · 8000 m³/h · Ceiling-mounted
HEAT PUMP
Rated cooling capacity, kW73
Rated heating capacity, kW76
Supply voltage380V/3PH/50Hz
Fresh air — airflow, m³/h8000
Fresh air — E.S.P, Pa400
Fresh air — motor, kW4
Exhaust air — airflow, m³/h8000
Exhaust air — E.S.P, Pa380
Exhaust air — motor, kW4
Compressor power, kW8.05
RefrigerantR410A
Energy-recovery efficiency>92%
Mounting orientationCeiling-mounted
Net weight, kg920
InAir RHP INA-HLN-080A1-DC
Energy recovery diagram
DC-Inverter Heat Pump · Energy Recovery (Sensible & Latent)
73 kW cooling · 76 kW heating.
R410A · >92% energy recovery · 380V 3-phase.
Adjusted to Indian Subcontinent specifications · −5 °C to +48 °C.
Fan performance
Indicative curve · fresh-air operating point from datasheet
016673333500066678333100000120240360480600 8000 m³/h @ 400 Pa Air volume (m³/h) Static pressure (Pa)
Two-stage energy recovery (sensible & latent)
Cross-flow core (1st stage) + DX heat pump (2nd stage) · built for Indian conditions
1st stageCross-flow total energy-recovery core
2nd stageDC-inverter scroll DX system
CompressorHigh-pressure chamber scroll
Control accuracy±2 °C
Group controlRS485 · up to 32 AHU/PLC
Safety protectionHi/Lo pressure · overcurrent · phase
Indicative figures for this model; confirm with our engineering team before specifying. Data per official INAIR datasheet. The latest data can be verified in the current selection software. INAIR reserves the right to introduce changes of parameters and sizes in the process of improvement of the air handling units.
sales@in-air.in
040-49952323
www.in-air.in
InAir · RHP Heat-Pump Energy Recovery AHU (Sensible & Latent)
INA-HLN-080A1-DC
Dimensions & air connections · Ceiling-mounted
DIMENSIONS
Unit outline dimensions (mm)
Ceiling-mounted · L×W×H = 4220×1240×2980 mm · per official INAIR datasheet
INA-HLN-080A1-DC outline dimensions
Overall dimensions
LWHWeight
422012402980920 kg
Air connection sizes (mm)
Fresh air inletSupply outlet
475x1075600x400
Return air inletExhaust outlet
475x1075600x400
OA – outdoor intake · SA – supply air · RA – return air · EA – exhaust air
Indicative figures for this model; confirm with our engineering team before specifying. Data per official INAIR datasheet. The latest data can be verified in the current selection software. INAIR reserves the right to introduce changes of parameters and sizes in the process of improvement of the air handling units.
sales@in-air.in
040-49952323
www.in-air.in