An ERV needs little routine care, but its filters do the hardest work and must be kept clean. In Indian cities, outdoor air carries dust and PM2.5 for much of the year, so filters load faster than in the countries where most ERVs were first designed. A clogged filter reduces airflow, and with less air the unit no longer clears CO₂ from the rooms.

What to check, and how often

PartWhat to doTypical interval
Pre-filterVacuum or wash, let it dry fully, refitEvery 1–3 months, more often in dusty seasons
MERV-13 filterReplace (not washable)When the filter alarm shows, or about every 6–12 months
HEPA-13 filterReplace (not washable)When the filter alarm shows, or about every 12 months
Carbon filterReplaceWhen odours return, or about every 6–12 months
Energy recovery coreInspect and clean as the manual saysAt the annual service
Drain and condensate trayCheck it runs clearAt the annual service, and before the monsoon
Outdoor grilles and louvresClear leaves, nests and dustEvery 3–6 months
Sensors and controllerCheck readings and settingsAt the annual service

These are typical intervals. The real interval depends on the city, the season, the building's surroundings and the hours the unit runs. Your InAir service plan states the intervals for your unit.

Why filter grade matters

MERV-13 filters are tested under ASHRAE Standard 52.2 and capture at least 85% of particles of 1–3 µm and 90% of 3–10 µm [1]. HEPA-13 (H13) filters, classed under EN 1822, capture at least 99.95% of particles at their most penetrating size [2]. Fit a replacement of the same grade, or higher only if the unit's fans are rated for the extra resistance.

Signs the unit needs attention

  • Less air from the diffusers than usual
  • CO₂ readings on the sensor staying high when the room is occupied
  • A filter alarm on the controller
  • New noise or vibration from the unit
  • Water around the unit or a musty smell during the monsoon

What the InAir service visit covers

An InAir service visit cleans or replaces the filters, inspects the energy recovery core, checks fans, drain, dampers and controls, and measures airflow at the outlets. Book a visit through the free site survey form or on WhatsApp.

Sources

  1. ANSI/ASHRAE Standard 52.2, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size (MERV ratings). https://www.ashrae.org/technical-resources/bookstore/standard-52-2
  2. EN 1822 / ISO 29463 high-efficiency filter classes (H13: at least 99.95% at the most penetrating particle size). https://airfiltration.mann-hummel.com/en-uk/insights/filter-classification/din-en-1822.html
Frequently Asked Questions
Pre-filters are cleaned every 1–3 months. MERV-13 and HEPA-13 filters are replaced when the filter alarm shows, typically every 6–12 months, sooner in dusty or high-AQI seasons.
Only the pre-filter. MERV-13, HEPA-13 and carbon filters are replaced, not washed.
Airflow falls, the unit brings in less fresh air, CO₂ rises in the rooms, and the fans work harder.
The core is inspected at the annual service and cleaned in the way the unit's manual sets out.