← Back to all applications
Commercial

Office and Commercial Building Ventilation

An office of 50 people on 500 m² needs about 970 m³/h of fresh air under ASHRAE 62.1. In a controlled Harvard study, office workers’ cognitive scores were about 15% lower at around 945 ppm CO₂ and about 50% lower at around 1,400 ppm than at 550 ppm. InAir supplies ERVs and heat pump AHUs that deliver filtered, pre-cooled fresh air to every floor.

Last updated: · Reviewed by the InAir engineering team

Offices and commercial buildings ventilation by InAir

Key facts

~15% lowercognitive scores at ~945 ppm CO₂ vs ~550 ppm[1]
6 of 9decision-making scales dropped at 1,000 ppm vs 600 ppm[2]
~970 m³/hfresh air for 50 people on 500 m² (ASHRAE 62.1)[3]

Why offices and commercial buildings need dedicated ventilation in India

Sealed glass buildings depend on mechanical fresh air

Most Indian offices run split or VRF AC that recirculates room air. Unless a fresh air system is built in, the outdoor air supply depends on leaks and door openings, and CO₂ rises through the working day.

Fresh air affects how well people think

In a double-blind study, office workers scored about 15% lower on cognitive tests at around 945 ppm CO₂ and about 50% lower at around 1,400 ppm than at 550 ppm[1]. In another, six of nine decision-making scales fell at 1,000 ppm compared with 600 ppm[2].

Bringing in outdoor air costs cooling energy unless it is recovered

Outdoor air at 35–45°C adds load to the AC. An ERV transfers heat and moisture from the outgoing air to the incoming air, so fresh air reaches the AC close to room conditions. Indoor VOCs from furniture, carpets and printers, which run up to ten times higher indoors[4], are diluted at the same time.

How much fresh air is needed?

ASHRAE 62.1 sets office ventilation at 5 cfm per person plus 0.06 cfm per sq ft, and conference rooms at the same rates with higher occupancy[3]. NBC 2016 Part 8 covers air conditioning and mechanical ventilation in Indian buildings[5].

SpaceASHRAE 62.1 rateFresh air (m³/h)Typical InAir selection
Open office, 500 m², 50 people573 cfm973 m³/hVentura INA-QRXF-1000 class
Conference room, 40 m², 20 people126 cfm214 m³/hRevita INA-MFQR-250
Office floor, 1,500 m², 150 people~1,720 cfm~2,900 m³/hVentura INA-QRXF-3000-FS or RHP 3,000
Whole building, 10 floors~17,200 cfm~29,000 m³/hMultiple Ventura / RHP units

With demand control, fans run at lower speed when floors are part-empty. InAir’s occupancy study measured about 40% fan-energy savings against constant running[6]. Conversion: 1 cfm = 1.699 m³/h.

Recommended InAir system

NeedInAir solution
Office floors with VRF or split ACRevita / Ventura ERV (Ventura) ducted to each zone
Buildings needing fresh-air cooling and dryingRHP heat pump ERV AHU
Meeting rooms and cabinsRevita ERV with IAQ sensors and smart controls
Toilets and pantriesToilet exhaust fans and Inline duct fans
Basement car parksJet fans

Full technical data: Revita · Ventura · RHP spec sheets.

How InAir delivers it

  1. Free site survey. An InAir engineer visits, measures the space, notes occupancy and heat sources, and checks routes for ducts and outdoor intakes.
  2. Airflow sizing. Fresh air and exhaust are sized to ASHRAE 62.1 / 62.2 and NBC 2016 Part 8, and checked against a CO₂, humidity or heat-removal target for the space.
  3. Equipment and filter selection. We select units, fans and filters (MERV-13, HEPA-13 or carbon) for the city’s outdoor air and the space’s needs, and share a written proposal.
  4. Installation and commissioning. Our team installs, then measures and balances supply and exhaust airflow at each outlet before handover.
  5. Monitoring and service. Optional sensors track CO₂, PM2.5 and humidity. Filters are changed on a scheduled service plan.

Frequently asked questions

Under ASHRAE 62.1, 5 cfm per person plus 0.06 cfm per sq ft: about 970 m³/h for 50 people on 500 m².
Outdoor air adds load, but an ERV recovers most of the cooling energy from the outgoing air, so the added load is far lower than opening windows or using plain fans.
Yes. The ERV supplies pre-treated fresh air into each zone and the VRF units handle the remaining cooling.
It is optional but useful: CO₂ sensors let the fans follow occupancy, which cuts fan energy on part-empty floors.

References

  1. Allen JG et al. (2016). Associations of cognitive function scores with carbon dioxide, ventilation, and VOC exposures in office workers. Environmental Health Perspectives 124:805–812. https://doi.org/10.1289/ehp.1510037
  2. Satish U et al. (2012). Is CO2 an indoor pollutant? Direct effects of low-to-moderate CO2 concentrations on human decision-making performance. Environmental Health Perspectives 120:1671–1677. https://doi.org/10.1289/ehp.1104789
  3. ANSI/ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality (Table 6-1, Ventilation Rate Procedure). https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2
  4. US EPA, Volatile Organic Compounds’ Impact on Indoor Air Quality. https://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-indoor-air-quality
  5. Bureau of Indian Standards, National Building Code of India 2016 (SP 7), Part 8 Building Services. https://bis.gov.in/others/national-building-code/
  6. InAir case study: Occupancy-based ventilation fan energy. https://www.in-air.in/case-studies/occupancy-based-ventilation-fan-energy/

Book a free site survey

An InAir engineer will survey your space, size the fresh air and exhaust, and send a written proposal. Available across 15 Indian cities.