Office and Commercial Building Ventilation
An office of 50 people on 500 m² needs about 970 m³/h of fresh air under ASHRAE 62.1. In a controlled Harvard study, office workers’ cognitive scores were about 15% lower at around 945 ppm CO₂ and about 50% lower at around 1,400 ppm than at 550 ppm. InAir supplies ERVs and heat pump AHUs that deliver filtered, pre-cooled fresh air to every floor.

Why offices and commercial buildings need dedicated ventilation in India
Sealed glass buildings depend on mechanical fresh air
Most Indian offices run split or VRF AC that recirculates room air. Unless a fresh air system is built in, the outdoor air supply depends on leaks and door openings, and CO₂ rises through the working day.
Fresh air affects how well people think
In a double-blind study, office workers scored about 15% lower on cognitive tests at around 945 ppm CO₂ and about 50% lower at around 1,400 ppm than at 550 ppm[1]. In another, six of nine decision-making scales fell at 1,000 ppm compared with 600 ppm[2].
Bringing in outdoor air costs cooling energy unless it is recovered
Outdoor air at 35–45°C adds load to the AC. An ERV transfers heat and moisture from the outgoing air to the incoming air, so fresh air reaches the AC close to room conditions. Indoor VOCs from furniture, carpets and printers, which run up to ten times higher indoors[4], are diluted at the same time.
How much fresh air is needed?
ASHRAE 62.1 sets office ventilation at 5 cfm per person plus 0.06 cfm per sq ft, and conference rooms at the same rates with higher occupancy[3]. NBC 2016 Part 8 covers air conditioning and mechanical ventilation in Indian buildings[5].
| Space | ASHRAE 62.1 rate | Fresh air (m³/h) | Typical InAir selection |
|---|---|---|---|
| Open office, 500 m², 50 people | 573 cfm | 973 m³/h | Ventura INA-QRXF-1000 class |
| Conference room, 40 m², 20 people | 126 cfm | 214 m³/h | Revita INA-MFQR-250 |
| Office floor, 1,500 m², 150 people | ~1,720 cfm | ~2,900 m³/h | Ventura INA-QRXF-3000-FS or RHP 3,000 |
| Whole building, 10 floors | ~17,200 cfm | ~29,000 m³/h | Multiple Ventura / RHP units |
Recommended InAir system
| Need | InAir solution |
|---|---|
| Office floors with VRF or split AC | Revita / Ventura ERV (Ventura) ducted to each zone |
| Buildings needing fresh-air cooling and drying | RHP heat pump ERV AHU |
| Meeting rooms and cabins | Revita ERV with IAQ sensors and smart controls |
| Toilets and pantries | Toilet exhaust fans and Inline duct fans |
| Basement car parks | Jet fans |
How InAir delivers it
- Free site survey. An InAir engineer visits, measures the space, notes occupancy and heat sources, and checks routes for ducts and outdoor intakes.
- Airflow sizing. Fresh air and exhaust are sized to ASHRAE 62.1 / 62.2 and NBC 2016 Part 8, and checked against a CO₂, humidity or heat-removal target for the space.
- Equipment and filter selection. We select units, fans and filters (MERV-13, HEPA-13 or carbon) for the city’s outdoor air and the space’s needs, and share a written proposal.
- Installation and commissioning. Our team installs, then measures and balances supply and exhaust airflow at each outlet before handover.
- Monitoring and service. Optional sensors track CO₂, PM2.5 and humidity. Filters are changed on a scheduled service plan.
Related InAir case studies
Frequently asked questions
How much fresh air does an office need?
Does fresh air increase AC load?
Can it work with an existing VRF system?
Is CO₂ monitoring needed?
References
- Allen JG et al. (2016). Associations of cognitive function scores with carbon dioxide, ventilation, and VOC exposures in office workers. Environmental Health Perspectives 124:805–812. https://doi.org/10.1289/ehp.1510037
- Satish U et al. (2012). Is CO2 an indoor pollutant? Direct effects of low-to-moderate CO2 concentrations on human decision-making performance. Environmental Health Perspectives 120:1671–1677. https://doi.org/10.1289/ehp.1104789
- ANSI/ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality (Table 6-1, Ventilation Rate Procedure). https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2
- US EPA, Volatile Organic Compounds’ Impact on Indoor Air Quality. https://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-indoor-air-quality
- Bureau of Indian Standards, National Building Code of India 2016 (SP 7), Part 8 Building Services. https://bis.gov.in/others/national-building-code/
- InAir case study: Occupancy-based ventilation fan energy. https://www.in-air.in/case-studies/occupancy-based-ventilation-fan-energy/
Book a free site survey
An InAir engineer will survey your space, size the fresh air and exhaust, and send a written proposal. Available across 15 Indian cities.