Library Fresh Air Ventilation Systems
Libraries need fresh air for readers and steady humidity for books. ASHRAE 62.1 sets 5 cfm per person plus 0.12 cfm per sq ft, about 1,390 m³/h for 60 readers on 400 m². Archives recommend 45–50% relative humidity for paper, and mould can grow when humidity stays above 65%. InAir supplies ERVs with dehumidification to hold both.

Why libraries need dedicated ventilation in India
Reading rooms are quiet, full and closed
Students and readers sit for hours in closed, air-conditioned rooms. Without fresh air, CO₂ rises through the afternoon, and studies link raised CO₂ to slower, less accurate mental work[3].
Paper needs stable humidity
Temperature and humidity are the main controls in preserving library and archive collections, and wide swings in either cause damage[4]. The National Archives of Australia recommends 45–50% relative humidity for specialised paper storage and notes that mould can grow when humidity stays above 65% for a considerable period[2].
Indian monsoons push humidity far above that
Outdoor air in the monsoon can be close to saturated. Bringing it in untreated raises indoor humidity and risks mould on bindings and shelves. Fresh air has to be dried before it reaches the stacks.
How much fresh air is needed?
ASHRAE 62.1 sets libraries at 5 cfm per person plus 0.12 cfm per sq ft[1].
| Space | ASHRAE 62.1 rate | Fresh air (m³/h) | Typical InAir selection |
|---|---|---|---|
| Reading room, 400 m², 60 readers | 817 cfm | 1,388 m³/h | Ventura INA-QRXF-1500-C |
| Study hall, 200 m², 80 students | 658 cfm | 1,118 m³/h | Ventura INA-QRXF-1300-C |
| Stack room, 300 m², 5 staff | 412 cfm | 700 m³/h | Revita INA-MFQR-800 + dehumidifier |
| Archive / rare books room | Humidity-led | Low, constant | Water-coil fresh air dehumidifier |
Recommended InAir system
| Need | InAir solution |
|---|---|
| Reading rooms | Revita / Ventura ERV with IAQ sensors and smart controls |
| Stacks and archives | Fresh air dehumidifier (rotary) or Water-coil fresh air dehumidifier |
| Humid cities | RHP heat pump ERV AHU |
| Dust from outdoor air | HEPA H13 and carbon filter boxes |
| Distribution | Flat ducting and dampers and Diffusers and grilles |
How InAir delivers it
- Free site survey. An InAir engineer visits, measures the space, notes occupancy and heat sources, and checks routes for ducts and outdoor intakes.
- Airflow sizing. Fresh air and exhaust are sized to ASHRAE 62.1 / 62.2 and NBC 2016 Part 8, and checked against a CO₂, humidity or heat-removal target for the space.
- Equipment and filter selection. We select units, fans and filters (MERV-13, HEPA-13 or carbon) for the city’s outdoor air and the space’s needs, and share a written proposal.
- Installation and commissioning. Our team installs, then measures and balances supply and exhaust airflow at each outlet before handover.
- Monitoring and service. Optional sensors track CO₂, PM2.5 and humidity. Filters are changed on a scheduled service plan.
Related InAir case studies
Frequently asked questions
What humidity should a library be kept at?
How much fresh air does a reading room need?
Will fresh air raise humidity in the monsoon?
Can it be fitted in an old library building?
References
- ANSI/ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality (Table 6-1, Ventilation Rate Procedure). https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2
- National Archives of Australia, Preserving paper documents and artworks: temperature and humidity. https://www.naa.gov.au/information-management/storing-and-preserving-information/preserving-information/preserving-paper-documents-and-artworks
- Allen JG et al. (2016). Associations of cognitive function scores with carbon dioxide, ventilation, and VOC exposures in office workers. Environmental Health Perspectives 124:805–812. https://doi.org/10.1289/ehp.1510037
- Northeast Document Conservation Center, Preservation Leaflet 2.1: Temperature, Relative Humidity, Light, and Air Quality. https://www.nedcc.org/free-resources/preservation-leaflets/2.-the-environment/2.1-temperature,-relative-humidity,-light,-and-air-quality-basic-guidelines-for-preservation
Book a free site survey