Sizing tool

Air Changes per Hour and Exhaust Fan Size Calculator

Pick a room and enter its size. The calculator gives the airflow it needs in m³/h and cfm from the air change rates in India's National Building Code, checks it against the ASHRAE minimum fan rates, and suggests a duct size. Bedrooms and living rooms are sized by the number of people, the way they should be.

Last updated: · Reviewed by the InAir engineering team

Your room

–room volume
––
––

Conversions: 1 cfm = 1.699 m³/h; 1 L/s = 3.6 m³/h. For ducts longer than about 8 m, or with more than three bends, go one size up. A first estimate only: fans and ducts are confirmed at a free site survey.

How the figure is worked out

Toilets, bathrooms, kitchens and utility rooms are sized by air changes: airflow (m³/h) = room volume (m³) × air changes per hour. The default rates come from the table of recommended air changes in the National Building Code of India, Part 8[1][2]. The result is then checked against the minimum fan rates in ASHRAE 62.2, the US standard for homes[3], and the larger figure is shown.

Bedrooms, living rooms and offices are sized by people, because what builds up there is what people breathe out. A resting adult breathes out about 12 litres of CO₂ an hour; outdoor air holds about 425 ppm. To hold a room at about 1,000 ppm takes about 21 m³/h of outdoor air per person, and about 32 m³/h for 800 ppm. That agrees with the 20–30 m³/h per person the NBC asks for[1]. For a typical bedroom it works out to only one or two air changes an hour, not the 6–8 sometimes quoted, which would bring in three to four times more hot, humid outdoor air than the room needs.

Duct size is the round duct that carries the airflow at the chosen speed, rounded up to a standard size. For small fans, ASHRAE 62.2 also lists minimum duct sizes: 100 mm (4 in) up to 50 cfm, 125 mm up to 100 cfm and 150 mm up to 150 cfm, for runs under about 8 m with no more than three bends[4].

RoomNBC air changes per hourASHRAE 62.2 minimum
Toilet, bathroom6–1050 cfm (85 m³/h) when in use, or 20 cfm (34 m³/h) continuous
Shower room15–20as bathroom
Kitchen (home)6 minimumHood 100 cfm (170 m³/h); enclosed kitchen without hood 5 ACH continuous or 300 cfm (510 m³/h) when cooking
Utility room / laundry15–20 / 10–30–
Bedroom / living room2–4 / 3–6 (or 20–30 m³/h per person)Whole home: 0.03 cfm per sq ft + 7.5 cfm per person
Basement, cellar3–10–
Garage6–8–
Restaurant, canteen8–12–

The full table, with UK and ASHRAE commercial rates and worked examples, is in air changes per hour by room. For a whole home's fresh air, use the ERV sizing calculator.

InAir fans and fresh air for each room

Frequently asked questions

Multiply the room's length, width and height in metres to get its volume in m³. Airflow in m³/h = volume × air changes per hour. A 2.4 × 1.5 × 2.7 m toilet is 9.7 m³; at 8 air changes an hour it needs about 78 m³/h, which ASHRAE 62.2 rounds up to at least 85 m³/h (50 cfm).
The National Building Code recommends 6–10 air changes per hour for toilets and bathrooms, and 15–20 for shower rooms. ASHRAE 62.2 sets a minimum fan of 50 cfm (85 m³/h) when in use. For most Indian bathrooms that means a fan of about 85–150 m³/h.
At least 6 air changes per hour under the NBC. A ducted hood should move at least 100 cfm (170 m³/h) under ASHRAE 62.2; an enclosed kitchen without a hood needs 5 air changes per hour continuously or 300 cfm (510 m³/h) while cooking.
No. A bedroom needs fresh air for the people in it: about 21 m³/h per person to keep CO₂ near 1,000 ppm, in line with the NBC's 20–30 m³/h per person. That is usually one to two air changes an hour. Sizing at 6–8 air changes over-ventilates the room and adds a large cooling and moisture load to the AC.
Size the duct for the airflow at a modest speed, about 3 m/s for quiet branch ducts. ASHRAE 62.2 gives minimum round duct sizes for short runs: 100 mm up to 50 cfm, 125 mm up to 100 cfm and 150 mm up to 150 cfm. Go one size up for long runs, flexible duct or more than three bends.

References

  1. Bureau of Indian Standards, National Building Code of India, Part 8 (Building Services), Section 1, Table of recommended air changes, and clause on fresh air per person; values as published in the 2005 edition (SP 7:2005).
  2. CSIR, Guidelines on Ventilation, version 2.0 (2022), Table 1, reproducing the NBC 2016 air change rates. niti.gov.in
  3. ANSI/ASHRAE Standard 62.2-2022, Addendum e: Tables 5-1 and 5-2, local exhaust rates. ashrae.org
  4. ANSI/ASHRAE Standard 62.2-2016, Addendum u: Table 5.3, prescriptive duct sizing. ashrae.org
  5. IS 3103:1975, Code of practice for industrial ventilation. law.resource.org