ERV Sizing Calculator for Homes
Enter your home's floor area and number of bedrooms. The calculator gives the minimum continuous fresh air under ASHRAE 62.2 and the InAir unit typically fitted for a home of that size.
Your home
How the figure is worked out
For homes, ASHRAE 62.2 sets the minimum continuous whole-house rate: 0.03 cfm per sq ft of floor area plus 7.5 cfm per occupant, taking occupants as bedrooms + 1[1]. A 1,600 sq ft 3BHK therefore needs 0.03 × 1,600 + 7.5 × 4 = 78 cfm, or about 133 m³/h.
InAir then checks each bedroom against a CO₂ target, which usually calls for more air than the minimum. That is why the unit shown is larger than the calculated figure: it is sized so that each closed bedroom stays near 800 ppm CO₂ overnight[2].
| Home | ASHRAE 62.2 minimum | Minimum (m³/h) | Typical InAir selection |
|---|---|---|---|
| 2BHK, 1,100 sq ft (3 people) | 56 cfm | 95 m³/h | Revita INA-MFQR-250 |
| 3BHK, 1,600 sq ft (4 people) | 78 cfm | 133 m³/h | Revita INA-MFQR-350 |
| 4BHK, 2,400 sq ft (5 people) | 110 cfm | 187 m³/h | Revita INA-MFQR-500 |
| Villa, 6,000–8,000 sq ft | — | ~2,000 m³/h (design) | Ventura / RHP |
More on sizing: fresh air ventilation for homes and apartments · fresh air system for a 3BHK · fresh air rates for other building types.
Frequently asked questions
What formula does the calculator use?
Why is the InAir unit larger than the calculated minimum?
Does this work for offices, schools or shops?
Is the result a final design?
References
- ANSI/ASHRAE Standard 62.2, Ventilation and Acceptable Indoor Air Quality in Residential Buildings. https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2
- InAir case study: 3 BHK apartment, Hyderabad. https://www.in-air.in/case-studies/hyderabad-3bhk-apartment-erv/
Book a free site survey
An InAir engineer will survey your home, size the fresh air and exhaust, and send a written proposal. Available across 15 Indian cities.