← Back to all articles
Reference · Exhaust · Standards 7 min read By Abhilash Srinivas, Managing Director – InAir ·

Air changes per hour by room: NBC India and ASHRAE rates for toilets, kitchens and bedrooms

Toilets, kitchens and utility rooms need a set number of air changes an hour. Bedrooms need fresh air per person instead. Here are the published rates, the formula and the duct sizes.

Last updated:

InAir: Air changes per hour by room: NBC India and ASHRAE rates for toilets, kitchens and bedrooms
air changes per hourACPH calculationair changes per hour bathroomkitchen exhaust fan sizeNBC ventilation rates

Air changes per hour (ACH or ACPH) is the number of times a room's whole volume of air is replaced in an hour. For toilets, kitchens and utility rooms in India, the National Building Code recommends 6 to 20 air changes an hour depending on the room. Bedrooms and living rooms are better sized by the number of people in them. This page sets out the published rates, how to use them and where they go wrong. The air changes and exhaust fan size calculator does the arithmetic for your room.

The formula

Airflow (m³/h) = room volume (m³) × air changes per hour. Room volume is length × width × height in metres. To convert: 1 cfm = 1.699 m³/h, and 1 litre per second = 3.6 m³/h.

Example: a toilet of 2.4 m × 1.5 m with a 2.7 m ceiling holds 9.7 m³. At 8 air changes an hour it needs 9.7 × 8 = 78 m³/h. ASHRAE 62.2 sets a minimum of 50 cfm (85 m³/h) for a bathroom fan used intermittently, so choose at least 85 m³/h.

Recommended air changes by room (NBC India)

Bar chart of recommended air changes per hour by room under India's National Building Code
Ranges from the NBC's table of recommended air changes. Tap to enlarge.
RoomNBC air changes per hourNotes
Bedroom2–4Better sized by people: 20–30 m³/h per person
Living room3–6As above
Kitchen (home)6 minimumPlus a ducted hood over the hob
Toilet, bathroom6–10
Lavatory (public)6–15
Shower room15–20High moisture
Utility room15–20Washing machine, drying
Laundry10–30Commercial laundries at the top of the range
Basement, cellar3–10NBC allows 50% more below ground
Garage (private)6–8Basement car parks follow fire rules
Restaurant, canteen8–12Commercial kitchens are sized by appliance load
Gymnasium6 minimum
Factory, workshop8–10Fume sources need local extraction

Source: National Building Code of India, Part 8, Section 1, table of recommended air changes, as printed in SP 7:2005 and reproduced for NBC 2016 in CSIR's 2022 ventilation guidelines. The NBC notes the rates can be raised by half where a room is below ground or heavily used.

Minimum fan rates (ASHRAE 62.2 and 62.1)

Air change rates give a target. Fan minimums make sure a small room still gets a fan that clears it quickly. India has no separate residential fan standard, so InAir checks every room against ASHRAE 62.2, the US standard for homes, and ASHRAE 62.1 for other buildings.

RoomWhen in use (intermittent)Running continuously
Bathroom or toilet (home)50 cfm (85 m³/h)20 cfm (34 m³/h)
Kitchen, ducted hood100 cfm (170 m³/h)–
Enclosed kitchen, no hood300 cfm (510 m³/h)5 air changes per hour
Private toilet (other buildings)50 cfm (85 m³/h)25 cfm (42 m³/h)
Public toilet, per WC or urinal–50 cfm (85 m³/h); 70 cfm for heavy use
Shower room, per showerhead50 cfm (85 m³/h)20 cfm (34 m³/h)
Commercial kitchen–0.70 cfm per sq ft (12.8 m³/h per m²)
Janitor, trash rooms–1.0 cfm per sq ft (18 m³/h per m²)

Sources: ASHRAE 62.2-2022 Addendum e, Tables 5-1 and 5-2; ASHRAE 62.1-2022 Addendum x, Table 6-2. For comparison, the UK's Approved Document F (2021) asks for 15 l/s (54 m³/h) from a bathroom fan and 30 l/s (108 m³/h) from a kitchen hood ducted outside.

Why bedrooms should not be sized by air changes

Some guides size bedroom fresh air at 6–8 air changes per hour. That number belongs to toilets and kitchens, where smells and steam must be cleared quickly. In a bedroom, what builds up is the CO₂ and moisture people breathe out, so the fresh air needed depends on how many people are in it, not on the size of the room.

A resting adult breathes out about 12 litres of CO₂ an hour. With outdoor air at about 425 ppm, holding a bedroom near 1,000 ppm takes about 21 m³/h of outdoor air per person, and about 32 m³/h per person for 800 ppm. That sits inside the NBC's 20–30 m³/h per person.

Bar chart comparing bedroom fresh air sized by people with 6 and 8 air changes per hour
Two sleepers need about 42 m³/h. Sizing by air changes brings in five to six times as much outdoor air. Tap to enlarge.

Bringing in more air than the room needs is not harmless in India. In the monsoon, every extra 100 m³/h of untreated outdoor air in Mumbai adds about 0.88 kW of moisture for the AC to remove (see the home ventilation guide). Sizing by people, with energy recovery, keeps the air fresh without that penalty. Bedroom CO₂ and sleep explains why the CO₂ target matters.

Duct size for the airflow

A fan only delivers its airflow if the duct is large enough. Size the duct so the air moves at a modest speed: about 3 m/s in short branch ducts for quiet running, up to about 5 m/s in a main duct. ASHRAE 62.2 gives minimum round duct sizes for small fans on runs under 8 m with no more than three bends:

Fan airflowMinimum round duct (rigid)
Up to 50 cfm (85 m³/h)100 mm (4 in)
Up to 100 cfm (170 m³/h)125 mm (5 in)
Up to 150 cfm (255 m³/h)150 mm (6 in)
Up to 200 cfm (340 m³/h)180 mm (7 in)
Up to 250 cfm (425 m³/h)205 mm (8 in)
Up to 450 cfm (765 m³/h)255 mm (10 in)
Up to 800 cfm (1,360 m³/h)305 mm (12 in)

Flexible duct needs one size larger from 100 cfm upwards. Source: ASHRAE 62.2-2016 Addendum u, Table 5.3.

Three worked examples

  • Toilet, 2.4 × 1.5 × 2.7 m: 9.7 m³ × 8 = 78 m³/h. ASHRAE minimum 85 m³/h. Choose a fan of about 85–120 m³/h on a 100 mm duct.
  • Home kitchen, 3.0 × 2.5 × 2.8 m: 21 m³ × 6 = 126 m³/h. A ducted hood of at least 170 m³/h covers the hob; without a hood, size the wall or inline fan to at least 6 air changes and run it whenever cooking.
  • Bedroom, two people: 2 × 21 = 42 m³/h of filtered outdoor air, about 1.2 air changes in a 34 m³ room. Supplied through an ERV, it keeps CO₂ near 1,000 ppm overnight without loading the AC.

Common mistakes

  • Sizing the fan but not the duct, so a 150 m³/h fan delivers half that through a long 100 mm flexible pipe.
  • Running a bathroom fan with no gap under the door, so it cannot pull air in.
  • Using air changes for bedrooms and over-ventilating them.
  • Using an exhaust fan to ventilate a bedroom. It pulls in unfiltered air through gaps; see exhaust fan vs fresh air system.
  • Discharging bathroom exhaust into a shaft next to a fresh air intake.

Sources

  • Bureau of Indian Standards, National Building Code of India, Part 8, Section 1: recommended air changes and fresh air per person. SP 7:2005
  • CSIR, Guidelines on Ventilation v2.0 (2022), Table 1, reproducing NBC 2016 rates. niti.gov.in
  • ASHRAE 62.2-2022 Addendum e, Tables 5-1 and 5-2. ashrae.org
  • ASHRAE 62.1-2022 Addendum x, Table 6-2. ashrae.org
  • ASHRAE 62.2-2016 Addendum u, Table 5.3, duct sizing. ashrae.org
  • UK Approved Document F, Volume 1: Dwellings (2021), Tables 1.1 and 1.2. gov.uk
  • IS 3103:1975, Code of practice for industrial ventilation. law.resource.org
Frequently Asked Questions
The National Building Code recommends 6–10 air changes per hour for toilets and bathrooms. ASHRAE 62.2 also sets a minimum fan of 50 cfm (85 m³/h) when the room is in use.
At least 6 under the NBC. A ducted hood over the hob should move at least 100 cfm (170 m³/h); an enclosed kitchen without a hood needs 5 air changes per hour continuously or 300 cfm (510 m³/h) while cooking under ASHRAE 62.2.
The NBC lists 2–4, but bedrooms are better sized by people: about 21 m³/h of outdoor air per person keeps CO₂ near 1,000 ppm, within the NBC's 20–30 m³/h per person. For two sleepers in a typical bedroom that is about 1–1.5 air changes an hour.
Multiply room volume in m³ by the air changes per hour to get m³/h. Divide m³/h by 1.699 to get cfm.
No. That rate suits toilets and kitchens. In a bedroom it brings in several times more hot, humid outdoor air than the people need, which adds a large load on the AC in Indian summers and monsoons.
Ready to breathe better? Start with a free site survey.

Our engineers assess your home or building, recommend the right system and the right filter grade for your city, and give you a clear cost estimate. No obligation.