AC Load Savings Calculator for Fresh Air with Heat Recovery

Fresh air adds heat to your AC's work. Pick your city and enter the fresh air you bring in. The calculator shows the heat that air adds on an average afternoon in the hottest month, how much an ERV core recovering 89% of the sensible heat takes off, and what that saves in AC power, units and rupees. Moisture is shown separately.

Last updated: · Reviewed by the InAir engineering team

Your home and AC

––
––
––
––
––
––

89% applies to sensible heat only, from the tested 89–90% heat recovery of InAir's Revita and Ventura ERVs[1]. The moisture figure is the load untreated air would add; no recovery figure is claimed for it. A first estimate: your home's figures are worked out at a free site survey.

How the figure is worked out

Heat from fresh air. The heat an AC must remove from air equals the mass of air times the change in its heat content[2]. For the temperature part (sensible heat): heat (kW) = airflow (m³/h) ÷ 3,600 × air density (kg/m³) × 1.006 kJ/kg·K (plus a small term for the water vapour) × (outdoor − indoor temperature). Air density is worked out from each city's elevation and the average of the two temperatures, so Bengaluru's thinner air carries a little less heat than Mumbai's.

Outdoor temperature. The default is the average daily maximum of each city's hottest month, from the ERA5 reanalysis for 2015–2024[3]. Choose the daily average to see a figure closer to round-the-clock running. ERA5 averages over a grid of about 30 km, so peaks read slightly below city weather stations.

Heat recovery. An ERV passes the outgoing room air and the incoming outdoor air across a core. With 89% sensible recovery, the fresh air reaches the room at the indoor temperature plus 11% of the difference. For Delhi at 38.9 °C and 24 °C indoors, that is about 25.6 °C. The heat it no longer brings in, 1.49 kW for 350 m³/h, is what the AC is spared.

AC power and money. AC electricity saved (kW) = heat saved ÷ the AC's efficiency in W/W. Units a day = kW × hours; rupees = units × tariff; a month is 30 days. One ton of refrigeration is 3.516 kW[2].

Moisture. Moisture load (kW) = airflow ÷ 3,600 × density × (outdoor − indoor moisture content, kg/kg) × 2,501 kJ/kg, for each city's most humid month (average dew point) against a room at the set temperature and 50% humidity. In coastal cities it is larger than the summer heat load. It is shown so you can see it; the saving above does not include it.

Choosing the AC efficiency

Enter your AC's efficiency in W/W. Indian AC labels give ISEER, a seasonal figure. BEE's star levels for inverter ACs, as compiled in a 2025 UC Berkeley working paper, put 1-star at ISEER 3.3 and 5-star at 5.0 up to 2025, and 1-star at 3.5, 3-star at 4.3 and 5-star at 5.6 from 2026[4]. ISEER includes the part-load running that inverters do well, so on a hot afternoon the real ratio is lower than the label. The default of 3.5 W/W is a conservative middle; enter your own if you know it. If your label gives EER in Btu/h per W, divide by 3.413 to get W/W[2].

Choosing the tariff

The default of ₹8.9 a unit is the marginal tariff used in a 2025 UC Berkeley working paper on Indian AC efficiency[4]. Savings come off your highest slab, so use the top rate on your own electricity bill.

Results for six cities

350 m³/h of fresh air (InAir's usual size for a 3BHK), room at 24 °C, AC efficiency 3.5 W/W, 8 AC hours a day at ₹8.9 a unit, average afternoon high of the hottest month.

CityHottest month, afternoon highHeat from untreated airLeft after 89% recoveryAC power savedSaving a monthMoisture load, most humid month
DelhiMay, 38.9 °C1.67 kW0.18 kW426 W₹9103.03 kW (July)
MumbaiApril, 32.9 °C1.04 kW0.11 kW263 W₹5623.04 kW (June)
KolkataApril, 35.6 °C1.34 kW0.15 kW341 W₹7293.46 kW (June)
ChennaiJune, 35.2 °C1.30 kW0.14 kW330 W₹7053.02 kW (May)
HyderabadMay, 37.1 °C1.43 kW0.16 kW363 W₹7761.96 kW (September)
BengaluruApril, 33.7 °C1.01 kW0.11 kW258 W₹5501.39 kW (June)

These are afternoon figures for the hottest month. Nights, winter and the monsoon have smaller temperature differences, so a year's saving is lower than twelve times this. The ERV also runs its own fans: the INA-MFQR-350 draws 160 W at full flow[1]. A plain fresh air system needs fans too, so not all of that is extra.

Related tools and guides

Frequently asked questions

It depends on the city and the airflow. On an average May afternoon in Delhi (38.9 °C), 350 m³/h of untreated outdoor air brought to 24 °C adds about 1.67 kW of heat, or about 0.48 TR. In humid months the moisture it carries adds more.
An ERV with 89% sensible heat recovery removes about 89% of that heat before the air reaches the room. For 350 m³/h on a Delhi May afternoon, that is about 1.49 kW of heat, or about 426 W of AC electricity at an efficiency of 3.5 W/W.
Monsoon air carries far more water than an AC room, and removing it is a large part of the AC's load in coastal cities. The 89% figure applies to sensible heat, so the calculator shows the moisture load on its own and does not add a recovery figure for it.
Use your AC's efficiency in W/W. Labels show ISEER, a seasonal figure that is higher than the real ratio on a hot afternoon. 3.5 W/W is a conservative default; BEE's 2026 star bands for inverter ACs start at ISEER 3.5 for 1-star and 5.6 for 5-star.
No. The ERV runs supply and exhaust fans; the INA-MFQR-350 draws 160 W at full flow. A plain fresh air system needs fans too. Compare the AC power saved with the fan power to see the net effect for your city.
No. It is for the hottest month, at the afternoon high or the daily average you choose. Nights, winter and mild days have smaller temperature differences, so the annual saving is lower than twelve times the monthly figure.

References

  1. InAir spec sheet, Revita INA-MFQR-350: heat-recovery efficiency 89–90% (tested); power 160/145/140 W at high/medium/low. in-air.in/spec-sheets/ina-mfqr-350
  2. Bureau of Energy Efficiency, Energy Performance Assessment of HVAC Systems (chapter 9): heat load from air mass flow and enthalpy difference; 1 TR = 3.516 kW; EER = 3.413 × COP. beeindia.gov.in
  3. Hersbach H. et al., The ERA5 global reanalysis, Q J R Meteorol Soc (2020); daily temperature and dew point 2015–2024 for city-centre grid cells via the Open-Meteo historical weather API; InAir analysis.
  4. Abhyankar N., Dominguez J., Shah N., Jain N., Phadke A. India can avert power shortages and cut consumer bills with stronger AC efficiency standards. India Energy and Climate Center, UC Berkeley, working paper, March 2025: Table 1 (ISEER star levels) and marginal tariff of ₹8.9/kWh. iecc.gspp.berkeley.edu

Book a free site survey

An InAir engineer will work out the fresh air your home needs and the unit that delivers it, and send an installed price. Available across 15 Indian cities.