Air quality tool

Bedroom CO₂ Calculator: How High Will It Get by Morning?

Enter the people, the room size and the hours the door and window stay shut. The calculator shows the CO₂ level by morning, hour by hour, and the fresh air needed to stay under 1,000 ppm. With the defaults, two people in a 4 × 3 m bedroom reach about 2,590 ppm after 8 hours; about 32 m³/h of fresh air keeps them under 1,000 ppm.

Last updated: · Reviewed by the InAir engineering team

Your bedroom

––
––
––

Orange bars are above your target. The room is assumed to start at the outdoor level (aired before bed) and the air to be evenly mixed. A first estimate: InAir measures and sizes each bedroom at a free site survey.

How the figure is worked out

The formula. The calculator treats the bedroom as one well-mixed space. CO₂ comes in with outdoor air and from the people breathing; it leaves with the air that goes out. That gives the standard single-zone balance used for CO₂ tracer measurements[4]:

C(t) = Cout + (G ÷ Q) × (1 − e−Q·t/V)
G = people × litres an hour ÷ 1,000 (m³/h of CO₂), × 1,000,000 for ppm
Q = fresh air supply + leakage (air changes/h × V), m³/h
V = room volume, m³; t = hours since the room was closed
Sealed room (Q = 0): C(t) = Cout + G × t ÷ V

As t grows, the level settles at Cout + G ÷ Q, whatever the room size. So the outdoor air needed to hold a target is Q = G ÷ (target − Cout). For two people at 12 L/h each and 425 ppm outdoors, that is 0.024 × 1,000,000 ÷ 575 = 41.7 m³/h, or about 21 m³/h per person. Leakage counts towards it; the supply figure shown is what is left after leakage.

CO₂ per person. The default is 12 litres an hour, the rate for a resting adult. Persily and de Jonge's tables give 0.0029–0.0037 L/s (about 10–13 L/h) for adults aged 30 to 40 at 1 met, and put sleeping at 0.95 met[1]. Children breathe out less: for a child aged 6 to 10 at rest the same tables give 0.0023–0.0025 L/s, or about 8–9 L/h. For a child, lower the rate or count them as about three-quarters of an adult.

Outdoor CO₂. The global mean for 2025 was 425.6 ppm[2]. Cities run higher, near traffic especially, and ASHRAE notes large local swings above the global figure[4]. If you have a CO₂ monitor, read it outdoors for a few minutes and enter that.

Leakage. Even with the door and window shut, some air leaks in. The default of 0.3 air changes an hour comes from the median measured in 84 bedrooms near Copenhagen with window and door closed during sleep: 0.32 per hour[3]. We did not find a published measurement for Indian bedrooms. A room with a gap under the door, an AC pipe hole or old window frames may leak more; a new, tightly sealed room may leak less. Try 0.1 and 0.5 to see the range.

Worked example

Two adults in a 4 × 3 m bedroom with a 2.8 m ceiling (33.6 m³), outdoor air at 425 ppm, 12 L/h each, starting from outdoor air:

RoomOutdoor air inCO₂ after 3 hCO₂ after 8 h
Sealed (no leakage at all)0.0 m³/h2,570 ppm6,140 ppm
Door and window shut, 0.3 air changes/h of leakage10.1 m³/h1,840 ppm2,590 ppm
Leakier room, 0.5 air changes/h16.8 m³/h1,530 ppm1,830 ppm
1 air change/h33.6 m³/h1,100 ppm1,140 ppm
0.3 ACH leakage + 32 m³/h fresh air supply42.1 m³/h980 ppm1,000 ppm
0.3 ACH leakage + 54 m³/h fresh air supply64.1 m³/h800 ppm800 ppm

A sealed room climbs about 714 ppm every hour with two sleepers. With the default leakage it ends the night near 2,590 ppm. About 32 m³/h of supply on top of the leakage holds 1,000 ppm, and about 54 m³/h holds 800 ppm.

What the number means

CO₂ at these levels is a gauge of how much outdoor air the room gets, not a poison. The US workplace limit is 5,000 ppm averaged over 8 hours[5]. ASHRAE's position is that evidence for direct effects of CO₂ on health, sleep and performance at ordinary indoor levels is inconsistent[4].

Reference pointCO₂Source
Outdoor air, 2025 global meanabout 425 ppmNOAA[2]
Proposed bedroom target in a 2025 review of 17 sleep studies800 ppm or lessAkimoto et al.[6]
IGBC Class A / B / C (outdoor + 350 / 440 / 530)about 775 / 865 / 955 ppm at 425 outdoorsIGBC[7]
Disturbed sleep seen from about this level in the same reviewabout 1,000 ppmAkimoto et al.[6]
US workplace limit, 8-hour average5,000 ppmOSHA[5]

The full chart, the studies behind it and the common myths are in CO₂ levels explained. For what research has found about sleep in closed bedrooms, read bedroom CO₂ and sleep.

Where the model is too simple

  • Real air is not perfectly mixed. Near the pillow CO₂ reads higher than across the room.
  • An open door shares the bedroom's air with the rest of the flat, which raises the volume and usually the leakage too.
  • A split AC recirculates room air. It does not bring outdoor air in, so it does not count as fresh air supply.
  • An exhaust fan alone pulls replacement air from wherever it can, often the corridor or bathroom, not from outdoors.

Check it with a monitor

A CO₂ monitor with an NDIR sensor will show your room's real curve in a night or two. Place it at head height away from the pillow and away from the AC outlet, and read it on waking before the door is opened. Sensor accuracy and calibration matter[4]; see the air quality monitor buying guide. InAir's IAQ sensor reads PM2.5, temperature, humidity and VOC; it does not measure CO₂, so use a separate CO₂ monitor for this.

Related tools and guides

Frequently asked questions

It depends on the people, the room and the leakage. Two adults in a 33.6 m³ bedroom with 0.3 air changes an hour of leakage reach about 1,840 ppm after 3 hours and about 2,590 ppm after 8 hours, starting from outdoor air at 425 ppm.
About 21 m³/h of outdoor air per person, at 12 L/h of CO₂ each and 425 ppm outdoors. For two people that is about 42 m³/h in total, including whatever leaks in. To stay at 800 ppm it is about 32 m³/h per person.
Only for a while. A bigger room takes longer to fill up, but the level it settles at depends on the fresh air per person, not on the room size. Over a full night the difference shrinks.
No. A split AC cools and recirculates the same room air. It brings in no outdoor air, so CO₂ keeps building up while it runs.
It is not toxic; the US workplace limit is 5,000 ppm over 8 hours. It does mean the room is getting little outdoor air, so everything else people and furnishings give off builds up too. Small studies link such rooms to lighter sleep.
No. InAir's IAQ sensor reads PM2.5, temperature, humidity and VOC. To check CO₂, use a separate monitor with an NDIR CO₂ sensor and compare it with this calculator.

References

  1. Persily A, de Jonge L. Carbon dioxide generation rates for building occupants. Indoor Air 2017;27(5):868–879, Tables 2–4. pmc.ncbi.nlm.nih.gov
  2. NOAA Global Monitoring Laboratory, global annual mean CO₂: 425.63 ppm for 2025. gml.noaa.gov
  3. Fan X, Liao C, Bivolarova MP et al. Air change rates during sleep in Danish bedrooms. CLIMA 2022: median 0.32 h⁻¹ with window and door closed, 0.40 h⁻¹ under habitual conditions, 84 bedrooms. proceedings.open.tudelft.nl
  4. ASHRAE Position Document on Indoor Carbon Dioxide, approved 12 February 2025. ashrae.org
  5. OSHA Occupational Chemical Database, carbon dioxide: PEL 5,000 ppm (8-hour TWA). osha.gov
  6. Akimoto M, Fan X, Lan L, Sekhar C, Tanabe S, Wyon DP, Wargocki P. Science and Technology for the Built Environment 2025, doi:10.1080/23744731.2025.2531317; summary by Waseda University. eurekalert.org
  7. Indian Green Building Council, IGBC Health and Well-being Rating System: CO₂ Class A/B/C at 350/440/530 ppm above ambient, with inputs from ISHRAE Standard 10001. IGBC (PDF)

Book a free site survey

An InAir engineer will measure your bedrooms, work out the fresh air each one needs and send an installed price. Available across 15 Indian cities.