Ventilation ducts for Indian homes: which type, what size, and how to stop leaks and condensation
The duct decides how much of a fan's airflow reaches the room. Here is how to choose the type, size it, seal it and keep it dry in an Indian monsoon.
Last updated:

The right ventilation duct for an Indian home is usually a smooth, rigid round duct, sized so air moves at about 3–4 m/s, with every joint sealed. Flat duct suits short branches to each room, flexible duct only the last short connection, and any duct carrying AC-cooled air needs insulation with a vapour barrier. This guide explains why, with the standards behind each number.
Key points
- Size: ASHRAE 62.2 gives minimum round duct sizes for short runs; up to 450 cfm they work out at about 3–4 m/s. Go one size up for flexible duct.
- Type: rigid round duct for main runs, flat duct for low room branches, flexible duct only for final connections of 1.5 m or less (UK Approved Document F).
- Pressure: resistance rises with the square of air speed, and every bend, grille and filter adds to it. The ventilation unit has a fixed pressure budget.
- Leakage: seal and mechanically fix every joint; leaks waste fresh air and can pull dusty ceiling air into the system.
- Condensation: July dew points in Mumbai, Delhi and Kolkata average about 25 °C. A duct carrying 24 °C air through an unconditioned void will sweat unless it is insulated and vapour-sealed.
Round, flat or flexible: which duct type?
India's National Building Code says ductwork is generally made from galvanised steel (GI) sheet, with aluminium where cleanliness rules are strict, such as operating theatres. Homes also use plastic ducts: rigid PVC pipe, flat ABS duct and flexible foil duct. Each has a place.
| Duct | Where it fits | Watch out for |
|---|---|---|
| Rigid round, GI steel | Main runs, kitchen exhaust, commercial work; non-combustible | Needs sealed joints and insulation where it carries cold air |
| Rigid round, PVC | Bathroom exhaust and fresh air runs in homes | Not for kitchen exhaust: NBC asks for a non-combustible duct there |
| Flat ABS duct (for example 132 × 30 mm) | Low branches inside false ceilings, floors or skirting | Small open area, so each run carries less air |
| Flexible foil duct | The last connection to a grille or unit | Sags and kinks add resistance; keep it short and pulled taut |
The InAir flat ducting and air distribution range covers all four: a 132 × 30 mm ABS flat duct system with 90° and 45° bends, 10-way and 12-way distribution boxes with Φ100 or Φ150 mm round connections, PVC aluminium-foil flexible ducts from Φ80 to Φ315 mm in 8 m rolls, airflow control valves and non-return valves.
UK Approved Document F is stricter about flexible duct than most Indian practice: rigid ducts wherever possible, and flexible duct only for final connections of 1.5 m or less, pulled taut. ASHRAE 62.2 asks for flexible duct one size larger than rigid.
What size of duct do you need?
For short runs, ASHRAE 62.2 gives a minimum round duct size for each airflow. The table converts those sizes into air speed, so you can see what each size is asking the air to do. The table applies to runs of about 8 m or less with no more than three bends; longer or more complex routes need a calculated design.
| Fan airflow | Minimum rigid round duct | Air speed in that duct |
|---|---|---|
| 50 cfm (about 85 m³/h) | 100 mm | 3.0 m/s |
| 100 cfm (about 170 m³/h) | 125 mm | 3.8 m/s |
| 150 cfm (about 255 m³/h) | 150 mm | 4.0 m/s |
| 200 cfm (about 340 m³/h) | 180 mm | 3.7 m/s |
| 250 cfm (about 425 m³/h) | 205 mm | 3.6 m/s |
| 350 cfm (about 595 m³/h) | 230 mm | 4.0 m/s |
| 450 cfm (about 765 m³/h) | 255 mm | 4.2 m/s |
| 800 cfm (about 1,359 m³/h) | 305 mm | 5.2 m/s |
The NBC suggests 7.5 m/s or less near noise-sensitive areas and 1.5–2.5 m/s inside plenums. Homes sit well below the first figure: lower speed means less resistance and less noise.
Flat duct needs particular care. A 132 × 30 mm duct has an open area of 3,960 mm², the same as a round duct of about 71 mm. Push 100 m³/h through it and the air moves at about 7 m/s, against 3.5 m/s in a 100 mm round duct. That is why flat systems split the airflow: a round main duct feeds a distribution box, and each room gets its own flat branch carrying only its share.
Pressure loss: every metre, bend and grille counts
Every ventilation fan has a pressure budget. InAir's Revita INA-MFQR-350 ERV, for example, is rated at 230 Pa, and the INA-MFQR-150 at 170 Pa. Everything between the outdoor terminal and the room grille spends part of that budget: straight duct, bends, branches, dampers, filters, grilles and the outdoor cowl.
The US Department of Energy's fan sourcebook, written with the fan industry body AMCA, gives the rule behind this: the pressure loss across each component rises with the square of the air speed. Double the speed and the loss roughly quadruples. It also warns of the 'system effect': a bend placed right at a fan's outlet disturbs the airflow and costs more pressure than the bend alone would suggest.
- Keep the route short and the bends few. Approved Document F asks for both, plus ducts sized for the airflow.
- The NBC recommends spacing bends and branch take-offs at least four to five duct diameters apart.
- Approved Document F asks that every grille or terminal has a free area of at least 90% of its duct's free area, so the grille does not become the bottleneck.
Leakage: why sealed joints matter
A leaking duct does more than waste air. On a fan's suction side, leaks pull dusty ceiling air in; on the pressure side, they push damp bathroom air, kitchen smells or filtered fresh air into the ceiling void.
European standards grade ductwork airtightness in classes, originally A (leakiest) to D (tightest), now reorganised as ATC 1 to ATC 7 under EN 12237 for round ducts, EN 1507 for rectangular ducts and EN 16798-3. Few countries make ductwork tightness mandatory; Spain requires class ATC 4 for new and retrofitted buildings, according to the TightVent platform. India has no such rule for homes, so tightness depends on the installer. Approved Document F's baseline is simple: every joint mechanically secured and sealed, with rigid connectors and jubilee clips on flexible duct.
How much false-ceiling depth do ducts need?
Depth is set by the deepest point on the route: the unit, a crossing of two ducts, or a beam. Add up the parts.
| Item | Height it takes | Source |
|---|---|---|
| Revita ceiling ERV casing | 180–272 mm deep, depending on model | InAir spec sheets |
| Round duct, 100–150 mm | Its diameter, plus insulation where needed | ASHRAE 62.2 sizes above |
| Flat duct | 30 mm, plus fixings | InAir flat ducting range |
| Two ducts crossing | Both heights added together | — |
| Beam in the route | Beam depth, unless the duct goes round or through it | Site survey |
Flat duct and beam crossers exist for the tight spots. Settle the ceiling plan with the interior designer before the false ceiling is closed; changing a route afterwards means opening it.
Insulation and condensation in Indian AC homes
Water condenses on any surface colder than the dew point of the air touching it. The NBC is direct about this: ducts carrying chilled or heated air need insulation to prevent heat gain and both internal and external condensation, and a vapour seal is essential where moisture could reach the insulation.
Indian monsoon air makes this a real risk. Ten years of ERA5 weather data put the July mean dew point at 25.8 °C in Kolkata, 24.9 °C in Delhi and 24.6 °C in Mumbai, with Chennai close behind at 23.1 °C. A bare duct carrying air from a 24 °C AC room through a false ceiling or shaft open to that outdoor air will sweat, and the water drips onto the ceiling board.
Two situations need the most care. First, exhaust and return ducts carrying cool room air through an unconditioned void. Second, the reverse: a duct carrying humid outdoor air through a void cooled by the AC, where water can form inside the duct. Fresh air that has been cooled, as in InAir's heat-pump ERV units, which deliver air at 22–28 °C, needs insulated supply ducts. Our monsoon humidity guide explains the moisture load itself.
Fire and smoke basics
Fire rules matter most in apartment blocks and commercial buildings. The publicly available 2005 text of the National Building Code, Part 4, makes three points about ducts; check the current 2016 edition with your architect or fire consultant.
- Concealed spaces such as false ceilings and ducts tend to act as flues in a fire, so the code asks for fire stopping within them.
- Air-conditioning and ventilation systems serving more than one floor or fire area need dampers that close automatically in a fire, and controls that stop the fans unless they are part of smoke extraction.
- Kitchen exhaust fans must discharge through an outside wall or through a non-combustible duct leading directly outside, not through areas holding combustible materials.
How InAir checks this at the site survey
Every InAir installation includes a site survey, duct design, commissioning with measured airflow readings, and handover. For the ducts, the engineer checks:
- the airflow each room needs, and the duct size that carries it without exceeding the unit's pressure budget;
- the clear depth above the false ceiling, beam depths and every crossing point on the route;
- where flat duct is needed, and how the airflow splits at the distribution box;
- which ducts will carry cold air through warm, humid voids, and so need insulation and a vapour barrier;
- where the ducts leave the building, and whether the outdoor terminals keep exhaust away from fresh air intakes;
- access for cleaning and for servicing fans, dampers and filters.
Book a free site survey with a floor plan, or start with the ERV sizing calculator.
What it costs
InAir flat duct (132 × 30 mm, 2 m length) starts from ₹1,800. Flat duct fittings, air boxes and floor or wall outlet panels start from ₹100 each, and noise reducers, beam crossers and flexible duct (8 m) from ₹4,400 each, before GST. Installation and duct runs are quoted after the site survey.
Tentative pricing: actual prices may vary based on the site survey.
Common mistakes
- Running long lengths of flexible duct instead of rigid duct, then wondering why the airflow is low.
- Sizing the duct to fit the ceiling gap rather than the airflow.
- Leaving cold ducts bare in a humid void, or insulating them without a vapour barrier.
- Using plastic duct for kitchen exhaust.
Sources
- ASHRAE 62.2-2016 Addendum u: Table 5.3, prescriptive duct sizes, flexible duct one size up.
- UK Approved Document F, Volume 1 (2021): paragraphs 1.76–1.81 on rigid and flexible ducts, pressure loss, terminal free area and sealed joints.
- National Building Code of India 2005, Part 8, Section 3 (Bureau of Indian Standards): ductwork materials, plenum and duct velocities, insulation and vapour seals, noise control.
- National Building Code of India 2005, Part 4: fire stopping, fire dampers, kitchen exhaust ducts.
- US DOE and AMCA, Improving Fan System Performance: A Sourcebook for Industry: pressure loss and system effect.
- TightVent: ductwork airtightness FAQs: airtightness classes and national requirements.
- ERA5 reanalysis via the Open-Meteo historical weather API: daily dew points 2015–2024; InAir analysis.
- InAir product pages, spec sheets and price list (FY 2026–27).
Which duct is best for home ventilation in India?
What size duct does a bathroom exhaust fan need?
Is flat ducting as good as round ducting?
Do ventilation ducts need insulation in India?
Can I use PVC pipe as a ventilation duct?
How deep does the false ceiling need to be for ducting?