← Back to all applications
Education & research

Laboratory Ventilation: Fresh Air, Exhaust and Fume Hood Make-up Air

A laboratory needs once-through air: filtered outdoor air in, all air exhausted outside, and the lab kept slightly negative so fumes do not reach corridors. NBC lists 6–15 air changes an hour for laboratories, but fume hoods often set the real airflow. InAir supplies the fresh air and exhaust fans, not the fume hoods.

Last updated: · Reviewed by the InAir engineering team

InAir inline duct fan boxes used for laboratory make-up air and exhaust

Key facts

6–15 /hair changes for laboratories in NBC's air change table[1]
0 %recirculation: lab air is exhausted directly outdoors[2]
~1,254 m³/hexhaust from one 1.5 m fume hood at 100 fpm with an 18 in sash (our calculation)[4]

Why laboratories are ventilated differently

In an office, most of the air is cooled and sent round again, with a share of fresh air mixed in. A laboratory works the other way. Chemicals, solvents and odours mean the air should pass through once and leave the building.

  • OSHA's laboratory standard advises that laboratory air should not be recirculated but exhausted directly outdoors, that air in chemical labs should be continuously replaced, and that lab air pressure should be negative to the rest of the building[2].
  • ANSI/ASSP Z9.5-2022, the US laboratory ventilation standard, covers hood airflow, supply and exhaust systems, recirculation, commissioning and annual testing. It states that face velocity alone is not enough to prove a hood works; containment is checked by several tests[3].
  • Because all supply air is outdoor air, every cubic metre has to be filtered and cooled from outdoor conditions. In Indian summers and monsoons this is a large share of the lab's cooling load.

How much air does a lab need?

There is no single number. Codes and institutions give ranges, and a risk assessment of the work sets the final rate. This table shows the main references.

ReferenceWhat it says
NBC air change table (Part 8, Section 3)Laboratories: 6–15 air changes per hour[1]
OSHA 29 CFR 1910.1450, Appendix ANo recirculation; continuous replacement; negative pressure to the rest of the building[2]
Arizona State University lab design guide (2017)General lab: 6 air changes per hour occupied, 4 unoccupied (4 and 2 with demand-controlled ventilation)[4]
University of Edinburgh lab ventilation policyAim for 6–8 air changes per hour occupied, set back to 4 out of hours; evidence needed above 12[5]
Fume hood face velocity (ASU guide)Traditional hoods: average 80–120 fpm (about 0.4–0.6 m/s); high-performance hoods to the maker's minimum, typically 65 fpm[4]
Low-flow fume cupboards (Edinburgh)Often safe at 0.35 m/s with suitable sills; checked annually within ±10% of commissioning[5]

fpm = feet per minute. 100 fpm = 0.508 m/s. Indian labs often follow these US and UK references alongside NBC; your safety officer decides which applies.

Fume hoods set the make-up air

A fume hood is an exhaust device, and it exhausts a lot of air. Take a hood with a 1.5 m wide opening and the sash at 18 inches (0.457 m). Our calculation of the exhaust it needs:

Face velocityHood exhaustCompared with an 8 × 6 × 3 m lab
0.35 m/s (low-flow hood)864 m³/h6.0 air changes per hour on its own
80 fpm (0.41 m/s)1,002 m³/h7.0 air changes per hour
100 fpm (0.51 m/s)1,254 m³/h8.7 air changes per hour
120 fpm (0.61 m/s)1,505 m³/h10.5 air changes per hour

Lab volume 144 m³. NBC's 6–15 air changes per hour for this room is 864–2,160 m³/h.

One hood can pull as much air as the whole room's minimum ventilation. Every cubic metre it removes must be replaced, so the make-up air is sized from the hoods first and the room rate second. On a Delhi afternoon in May, when the average daily maximum is 38.9 °C (ERA5 data), cooling 1,254 m³/h of outdoor air to 24 °C takes about 6.3 kW of sensible cooling, roughly 1.8 tonnes of refrigeration, before any moisture is removed. That is for one hood.

Laboratory section showing make-up air supplied away from the fume hood, hood and general exhaust, and corridor air leaking in under the door
The make-up supply is set slightly below total exhaust so the lab stays negative. Tap to enlarge.
  • Supply air diffusers go away from the hood face. Z9.5 requires hoods to be placed so cross drafts do not upset them[3].
  • Make-up air is set slightly below total exhaust, so the lab stays negative to the corridor.
  • If hoods are variable air volume, the make-up air has to follow them as sashes open and close.

What InAir supplies, and what it does not

Part of the systemWho supplies it
Fume hoods, biosafety cabinets and their controlsThe laboratory furniture or hood supplier. InAir does not supply fume hoods.
Fume hood exhaust fans and stacksSpecified with the hood supplier for the chemicals in use; InAir matches the make-up air to them
Make-up and fresh air supply, filteredInAir cabinet fans, cabinet fans with filters, and HEPA and carbon filter boxes
General room exhaustInAir cabinet centrifugal or industrial radial fans
Offices, write-up rooms and corridors next to the labInAir Revita / Ventura ERVs with 89–90% heat recovery (tested)
Monsoon humidity in the make-up airWater-coil fresh air dehumidifier or the building's chilled water coils

InAir does not route fume hood exhaust, or general exhaust from rooms where hazardous chemicals are handled, through an ERV. OSHA's guidance is to exhaust lab air directly outdoors[2]. Heat recovery from lab exhaust is a decision for the lab's safety officer and design engineer, not a default.

How InAir checks this at the site survey

  1. The work and the hazards. What the lab does, what chemicals are used, and the safety officer's risk assessment and target air change rate.
  2. Hoods. Number, size, sash heights, face velocity and whether they are constant or variable volume, from the hood supplier.
  3. Room data. Floor area, height, doors, and which rooms the lab must stay negative to.
  4. Outdoor air. Where make-up air can be drawn from, away from hood stacks and exhausts, and the city's dust and humidity.
  5. Proposal and commissioning. Fan and filter selections, then measured supply and exhaust airflows and the pressure difference at each lab door.

What it costs

Lab ventilation is quoted after the site survey because the hood schedule drives it. Published starting prices for the parts InAir supplies are: cabinet centrifugal fans from ₹47,400, cabinet fans with filter from ₹75,900, and fresh air filter boxes from ₹14,800 each, before GST and installation.

Tentative pricing: actual prices may vary based on the site survey.

Common mistakes

  • Sizing supply air from the room's air changes and forgetting the hoods, so the lab goes strongly negative and doors whistle or slam.
  • Supply diffusers blowing across the hood face, which pulls fumes out of the hood.
  • Returning lab air to a central AHU to save cooling.
  • Placing the fresh air intake near a hood stack.
  • Bringing in untreated monsoon air, so labs run humid and instruments and samples suffer.
  • Treating face velocity as the only test of a hood[3].

Frequently asked questions

NBC's air change table gives 6–15 per hour for laboratories. Many institutions use 6 per hour when occupied and about 4 when empty, but the safety officer's risk assessment and the fume hoods set the real figure.
OSHA's lab guidance says laboratory air should not be recirculated but exhausted directly outdoors.
So that air flows into the lab from corridors and offices, and fumes do not leak out. OSHA's guidance is negative pressure to the rest of the building.
As much as it exhausts. A 1.5 m hood with an 18 in sash at 100 fpm exhausts about 1,250 m³/h, so about the same amount of filtered outdoor air must be supplied, minus a small offset to keep the lab negative.
No. InAir supplies the fresh air and make-up air units, filters and general exhaust fans, and works with your hood supplier on the balance.
Yes for offices and write-up areas. InAir does not put fume hood exhaust or hazardous lab exhaust through an ERV.

References

  1. Bureau of Indian Standards, National Building Code of India, Part 8, Section 3: recommended air changes per hour, laboratories (Table 5 in SP 7 Group 4, 2005 edition, Public.Resource.Org copy). https://archive.org/details/gov.in.is.sp.7.4.2005
  2. US OSHA, 29 CFR 1910.1450 Appendix A, National Research Council recommendations concerning chemical hygiene in laboratories. https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.1450AppA
  3. AIHA, The Synergist (June 2022): the updated ANSI/ASSP Z9.5-2022 laboratory ventilation standard. https://synergist.aiha.org/20220607-lab-ventilation-standard
  4. Arizona State University EHS, Laboratory Standard and Design Guide: Lab Ventilation (June 2017). https://www.asu.edu/ehs/design-guidelines/laboratory-ventilation.pdf
  5. University of Edinburgh, Laboratory Ventilation Policy and Guidance (2024). https://sustainability.ed.ac.uk/sites/default/files/2024-10/Lab%20ventilation%20policy%20and%20guidance.pdf
  6. Copernicus ERA5 reanalysis via Open-Meteo, historical weather API (Delhi May mean daily maximum, InAir analysis). https://open-meteo.com/en/docs/historical-weather-api

Book a free site survey

An InAir engineer will survey your space, size the fresh air and exhaust, and send a written proposal. Available across 15 Indian cities.