Fresh air checklist: what to ask your builder
Ten questions to put to a builder or developer before the false ceiling closes, and what a good answer looks like.
Last updated:

Ask the builder for four things in writing: how much filtered outdoor air each bedroom and the living room will get (in m³/h, and to which standard), what filter grade it passes through, how loud the unit is at the speed it will run, and how the filters will be reached and serviced. If a project has no answer beyond "windows and exhaust fans", it has no fresh air system.
Key points
- India's National Building Code puts the fresh air a person needs at 20–30 m³/h. That holds a bedroom at roughly 830–1,030 ppm of CO₂ (our calculation below).
- IGBC Green Homes asks for at least 5 cfm (about 8.5 m³/h) per person in air-conditioned rooms, and 6.5 cfm (about 11 m³/h) for its enhanced ventilation credit. Those are minimums for a rating, not comfort targets.
- An IGBC-rated project may meet the ventilation requirement with openable windows alone. Ask which route the project used.
- Ask for the filter by grade: MERV-13 captures at least 85% of 1–3 µm particles; HEPA H13 at least 99.95% at the most penetrating size.
- Noise, access and service decide whether residents keep the system switched on. Ask for dB at the running speed and look for the access panel.
Why ask now, before the false ceiling goes up
Fresh air is cheapest to add while a flat is being built. Ducts run inside the ceiling void and nobody has to break a finished ceiling. Once interiors are done, the choice narrows to boxed ducts or wall-mounted units; our guide to adding fresh air to a finished flat covers that route. Buyers of an under-construction flat have a short window to ask. Developers have a longer one, at the design stage, and it is when the decisions are cheapest.
The need is real in Indian cities. Flats are closed for air conditioning, against dust and against noise, and a closed bedroom fills with CO₂ overnight. Our guide to why indoor air gets polluted with the windows shut explains what builds up.
Fresh air rate: which number to ask for
Three sets of figures turn up in Indian project specifications. They differ a lot, so ask the builder which one the design follows and what it gives per person.
| Benchmark | What it says | Per person (m³/h) | CO₂ it holds a room at* |
|---|---|---|---|
| NBC 2016 (as reproduced in the CSIR ventilation guidelines) | Fresh air of 20–30 m³/h per person, depending on space per person and activity | 20–30 | about 830–1,030 ppm |
| IGBC Green Homes v3, mandatory (RHW MR 2) | Air-conditioned rooms: at least 5 cfm per person in each habitable space | 8.5 | about 1,840 ppm |
| IGBC Green Homes v3, enhanced credit (RHW Credit 2, 2 points) | At least 6.5 cfm per person | 11.0 | about 1,510 ppm |
| ASHRAE 62.2 (whole home, continuous) | 0.03 cfm per sq ft plus 7.5 cfm per occupant (bedrooms + 1) | 31 for a 1,100 sq ft 2BHK with 3 people | about 810 ppm |
*InAir calculation for one resting adult, outdoor air at 425 ppm and fully mixed room air. Real rooms vary with occupancy, door position and how well the air mixes.
So "meets IGBC" and "enough fresh air to sleep well" are not the same claim. A useful target for a buyer is the NBC figure, per person, for every bedroom with the door shut. For a whole flat, the ERV sizing calculator gives the ASHRAE 62.2 minimum from floor area and bedrooms.
What IGBC Green Homes actually asks for
Many projects advertise an IGBC rating. In the Green Homes v3 rating system (abridged reference guide, 2019) the ventilation items sit in the Resident Health & Wellbeing section, worth 14 of the 100 points.
| IGBC item | Points | What it asks, in short | What to ask the builder |
|---|---|---|---|
| RHW MR 2: Ventilation Design | Mandatory | Openable windows and doors to outside as a share of carpet area (living spaces 10%, kitchens 8%, bathrooms 4% below five floors; 8%, 6% and 4% above), or 5 cfm of fresh air per person in air-conditioned rooms | Did the project comply by windows, or by mechanical fresh air? |
| RHW Credit 2: Enhanced Ventilation Design | 2 | Larger openings (12%, 10% and 5% below five floors) or 6.5 cfm per person | Which option was claimed, and for which rooms? |
| RHW Credit 3: Cross Ventilation | 4 | Share of regularly occupied rooms with openings in at least two orientations | Do bedrooms really cross-ventilate with the doors shut? |
| RHW Credit 5: Low VOC Materials | 2 | Eco-label certified paints, coatings, adhesives and sealants | Which paints and adhesives, and their VOC content |
| Toilet exhaust (under MR 2) | Part of MR 2 | Bathrooms can comply by an exhaust system of 50 cfm per 50 sq ft of toilet area, or by louvres | Fan rating in cfm or m³/h, and where it discharges |
Two details matter. First, the guide lets projects with unitary (split) ACs used for part of the year comply through openable windows and doors; only centralised air conditioning must meet the per-person fresh air figure. Second, IGBC's November 2025 clarification says doors used only now and then, such as the main door, cannot be counted for fresh air. A green rating can therefore mean good windows and no mechanical fresh air at all.
Filters: ask for the grade, not the word "filtered"
Outdoor air in most Indian cities needs filtering before it is blown into a bedroom. The Centre for Science and Environment's winter 2024–25 analysis put average PM2.5 at 175 µg/m³ in Delhi, 65 in Kolkata, 52 in Hyderabad, 50 in Mumbai, 37 in Bengaluru and 36 in Chennai. The WHO's 24-hour guideline is 15 µg/m³.
| Filter grade | What it captures (test standard) | Where it fits |
|---|---|---|
| Coarse pre-filter | Insects, leaves, large dust | Protects the main filter; not enough on its own |
| MERV-13 | At least 85% of 1–3 µm particles (ASHRAE 52.2) | Ordinary urban air; InAir's standard ERV filter |
| HEPA H13 | At least 99.95% at the most penetrating particle size (EN 1822) | High-AQI cities and sensitive occupants; optional on InAir ERVs |
Ask for the grade by name, the replacement filter's cost, and whether it is stocked in your city. Our guide to filter grades explains the classes.
Noise: ask for dB at the speed it will run
A fresh air unit that hums in the bedroom gets switched off. Ask for the sound figure at the speed the system will actually run, the distance it was measured at, and where the unit sits relative to the bedrooms. For fans, ASHRAE 62.2 caps continuously running fans at 1.0 sone and intermittent ones at 3 sones. InAir's spec sheets give 35 dB for the INA-MFQR-150 and 38 dB for the INA-MFQR-350 at full flow. Ductwork, grilles and the unit's position matter as much as the unit, which is why the drawings are worth asking for. See our noise guide.
Exhaust: toilets and kitchen
Fresh air in needs stale air out. NBC sets 6–10 air changes an hour for toilets and bathrooms and at least 6 for kitchens. ASHRAE 62.2 asks for 50 cfm (85 m³/h) intermittent or 20 cfm (34 m³/h) continuous from a bathroom. Ask for each fan's rating and where its duct ends: on an outside wall, or in a shaft that is open at the top. The air changes calculator turns room sizes into fan sizes.
Maintenance access and who services it
Filters need cleaning and changing on a schedule set by local air quality, so the unit must be reachable. Check that there is a removable panel or hatch under the unit, that the filter door opens without tools or ladders through furniture, and that the outdoor intake can be inspected. Ask who services the system after handover, who pays for filters, and what the annual maintenance contract covers. Our ERV maintenance guide lists what servicing involves.
The checklist
| # | Ask for | A good answer | A red flag |
|---|---|---|---|
| 1 | Fresh air per bedroom and living room, in m³/h, and the standard used | A room-by-room schedule; NBC 20–30 m³/h per person or more | "The windows open" or a single total for the flat |
| 2 | Outdoor air intake location | Shown on drawings, away from exhausts, kitchen outlets, DG sets and parking | Intake in a shaft or next to a toilet exhaust |
| 3 | Filter grade | MERV-13 standard, HEPA H13 option, replacement cost stated | "Filtered" with no grade |
| 4 | Heat recovery | Tested efficiency figure for the unit | Outdoor air blown straight into AC rooms |
| 5 | Noise at running speed | dB with distance, unit away from bedroom heads | Only the maximum airflow figure |
| 6 | Toilet and kitchen extract | Fan rating and discharge point for each | Fans ducted into the false ceiling |
| 7 | Air path between rooms | Door undercuts or transfer grilles | Tight doors on every room |
| 8 | Access and service | Access panel under the unit, named service provider, filter cost | Unit sealed above a gypsum ceiling |
| 9 | Green rating claims | Which IGBC credits, and by which compliance route | "IGBC rated" with no detail |
| 10 | Commissioning | Measured airflow at each grille, handed over in writing | No measurements at handover |
For developers: what to put in the specification
Write the fresh air requirement as a performance figure per room, not as a product name: airflow per person, filter grade, maximum noise in bedrooms, heat recovery, access for maintenance and measured airflow at handover. Size whole flats with the ERV sizing calculator, and use the InAir spec library for unit data. Common areas, clubhouses and basements need their own calculations; IGBC asks for those separately too. InAir supports project teams through its partners page.
How InAir checks this at the site survey
- Room-by-room occupancy from the floor plans, and the fresh air each bedroom needs with its door shut.
- The ceiling void, beam depths and a route for supply and extract ducts, or the outside walls available for wall-mounted units.
- Where the outdoor air intake and exhaust terminals can go, and what is near them.
- The filter grade your city's air quality calls for, MERV-13 or HEPA-13.
- Toilet and kitchen exhaust rates and where each discharges.
- Access for filter changes and servicing, planned with the interior designer.
- After installation: commissioning with measured airflow readings and a written handover.
What it costs
For one flat, a Revita ducted ERV starts from ₹2.1 lakh for a 1–2 BHK and from ₹2.6 lakh for a 3–4 BHK, before GST and installation. For a finished flat, a wall-mounted ERV starts from ₹1.4 lakh per unit. Ducting, grilles and installation are quoted after a free site survey. The price guide lists every range.
Tentative pricing: actual prices may vary based on the site survey.
Common mistakes
- Taking "IGBC rated" to mean the flat has mechanical fresh air.
- Asking for a total airflow for the flat instead of a figure for each bedroom.
- Accepting "filtered air" without a filter grade.
- Letting the false ceiling close before the access panel is marked.
- Treating toilet exhaust fans as the fresh air system. They remove air; they do not bring filtered air in.
- Placing the outdoor air intake beside a toilet exhaust or kitchen outlet.
Sources
- Indian Green Building Council, IGBC Green Homes Rating System Version 3.0, Abridged Reference Guide (2019): RHW MR 2, RHW Credits 2, 3 and 5. igbc.in
- IGBC, Addendum and Clarifications on Green Homes Version 3.0 (w.e.f. 1 November 2025). igbc.in
- CSIR, Guidelines on Ventilation (2022), reproducing NBC 2016 fresh air and air-change rates. niti.gov.in
- ASHRAE 62.2-2022 Addendum e: whole-house, bathroom and fan sound requirements. ashrae.org
- US EPA, What is a MERV rating? epa.gov
- Centre for Science and Environment, winter 2024–25 air pollution analysis of six megacities. cseindia.org
- WHO global air quality guidelines (2021). who.int
- InAir spec sheets INA-MFQR-150 and INA-MFQR-350, and price guide FY 2026–27.
What should I ask a builder about fresh air?
Does an IGBC-rated flat have a fresh air system?
How much fresh air does a bedroom need?
Which filter should a fresh air system have in an Indian city?
Can fresh air be added after possession?
What does a fresh air system for a new flat cost?