← Back to all articles
Explainer · TFA · Commercial 8 min read By Abhilash Srinivas, Managing Director – InAir ·

What is a TFA unit (treated fresh air)?

A TFA unit cools and dries 100% outdoor air before it enters a building. Here is what is inside one, where India uses it, and how it compares with an ERV and an AHU.

Last updated:

InAir RHP heat-pump ERV AHU on a rooftop beside a water-coil fresh air dehumidifier, two ways to treat fresh air
what is TFAtreated fresh air unitTFA unit HVACTFA vs ERV vs AHUfresh air unit India

A TFA, or treated fresh air unit, is an air handling unit that takes in only outdoor air, filters it and cools and dries it with its own chilled-water or DX coil before sending it into the building. In India it is the usual way large offices, hotels and hospitals get fresh air. Homes and smaller buildings more often use an ERV or a heat-pump ERV.

Key points

  • A TFA treats 100% outdoor air. A normal AHU or fan coil mostly recirculates room air.
  • Its main job in India is drying. In our ERA5 analysis, 1,000 m³/h of Mumbai monsoon air carries about 8.8 kW of moisture load against about 3.0 kW of heat in its hottest month.
  • A standard TFA has no exhaust connection, so the cooling in the air leaving the building is thrown away unless a wheel or plate is added.
  • India's Energy Conservation Building Code (ECBC 2017, §5.3.11) requires heat recovery of at least 50% effectiveness in large hotel and hospital systems that run on 70% or more outdoor air.
  • Where there is no chilled-water plant, a heat-pump ERV such as InAir's RHP range does a TFA's job and recovers energy as well.

What a TFA unit is

The name says what it does. Fresh air: the unit draws only outdoor air, never room air. Treated: it filters that air and conditions it, which in Indian weather mostly means cooling it and taking water out of it. The treated air then goes to the floors through ducts, or into the return side of the room units.

Inside, a TFA is built like any air handling unit: an outdoor air damper, a pre-filter and a fine filter, a cooling coil with a drain pan, a supply fan and controls. The coil is fed with chilled water from a central plant, or with refrigerant from a condensing unit (DX, direct expansion). What sets it apart from a recirculating AHU is the air it handles, not the parts.

Three rows of boxes showing the sections in a TFA unit, an ERV and a heat-pump ERV AHU, with arrows from outdoor air to the rooms
A TFA has a coil but no recovery core. An ERV has a core but no coil. A heat-pump ERV has both. Tap to enlarge.

Why Indian buildings use TFA units

Fresh air in India is hot for part of the year and wet for much of it. A room AC or fan coil is sized for the heat from people, lights and sun. It is not sized to dry large volumes of monsoon air, and it only removes moisture while its compressor runs. Putting a separate unit on the fresh air does three things: it takes the moisture out at one place, it lets the room units do only room cooling, and it keeps the building under slight positive pressure so dust and humid air do not leak in.

Bar chart of sensible and latent cooling load per 1,000 cubic metres per hour of outdoor air in Kolkata, Mumbai, Chennai, Delhi, Hyderabad and Bengaluru
In every city the moisture bar is longer than the heat bar. That is why a fresh air coil in India is really a dehumidifier. Tap to enlarge.

The chart uses ten years of ERA5 climate data, worked out by InAir. In Kolkata, 1,000 m³/h of untreated outdoor air in the most humid month carries 10.1 kW of moisture load, about 2.9 tons of refrigeration (TR), on an average day, not a design peak. A coil removes that water by cooling the air below its dew point. The US Department of Energy uses a 55 °F (12.8 °C) leaving dew point as the test condition for packaged dedicated outdoor air units. Air at that dew point holds about 9.2 g of water per kg, roughly what a room at 24 °C and 50% humidity holds (9.3 g/kg). So a well-run TFA hands the room air that adds almost no moisture.

Where you find TFA units in India

BuildingHow fresh air is usually handledWhy
Large offices and IT parksChilled-water TFA per floor or per block, feeding AHUs or VRF indoor unitsA chilled-water plant already exists; fresh air volumes are in thousands of m³/h
HotelsTFA supplying corridors and guest rooms, with toilet exhaust taking air outSteady occupancy, high humidity control needs
HospitalsTFA or 100% outdoor air AHUs for wards, operating theatres and isolation roomsInfection control needs filtered outdoor air and pressure control
Malls and auditoriumsUsually mixed-air AHUs with an outdoor air damper rather than a separate TFALarge spaces, varying crowds
Villas, clinics, schools, small officesERV, or heat-pump ERV where humidity is highNo chilled-water plant; smaller airflows
ApartmentsERV, ducted or wall-mountedSmall airflows; no central plant

How much fresh air each space needs comes first. India's National Building Code gives 20–30 m³/h of outdoor air per person; ASHRAE 62.1 sets rates by occupancy and floor area. Our guide to fresh air requirements under NBC and ASHRAE covers both.

TFA vs ERV vs AHU: which is which

TFA unitERVHeat-pump ERV AHU (InAir RHP)Recirculating AHU or FCU
Air it handles100% outdoor100% outdoor in, equal stale air out100% outdoor in, stale air outMostly room air
Cooling coilYes (chilled water or DX)NoYes (built-in DX heat pump)Yes
Energy recoveryOnly if a wheel or plate is addedYes, through a coreYes, core firstOptional
Dries monsoon airYesPartly; cannot dry below outdoor moistureYesOnly room air
Needs a chilled-water plantChilled-water type onlyNoNoChilled-water type only

The TFA vs ERV comparison covers the choice between the two in more depth. In short: a TFA cools and dries with a coil but wastes the exhaust air's cooling; an ERV recovers that cooling but has no coil, so it cannot bring wet monsoon air down to room moisture levels on its own. If the core moves only part of the moisture difference, incoming air always arrives wetter than the room.

What about energy recovery on a TFA?

A TFA's biggest running cost is its coil load, and much of that load could be met by the cool, dry air the building is already throwing out through toilets and kitchens. A heat recovery wheel or plate between the exhaust and fresh air streams lets the outgoing air pre-cool the incoming air before it reaches the coil.

India's code makes this compulsory in some cases. ECBC 2017, §5.3.11, says hospitality and healthcare buildings with systems larger than 2,100 litres per second (about 7,560 m³/h) and a minimum outdoor air supply of 70% must have air-to-air heat recovery with at least 50% recovery effectiveness. You will also see an ASHRAE 90.1 energy recovery figure quoted as a requirement. The clause usually cited sits in Appendix G, which sets the baseline building for energy modelling; it is a comparison point, not a rule a building must meet.

When a heat-pump ERV replaces a TFA

Most villas, clinics, schools and small offices have no chilled-water plant to feed a TFA coil. The InAir RHP heat-pump ERV AHU puts a recovery core and a DX heat pump in one box. Outdoor air passes the core first, then the heat pump cools and dries it to a set 22–28 °C. Its spec sheets list energy recovery above 92% and control accuracy of ±2 °C. The range runs from ceiling-mounted INA-HLN-B1 models to floor-standing INA-HLN-A1 models up to 8,000 m³/h, and every model needs a three-phase 380 V supply.

For a single humid room or a small zone, InAir also has fresh air dehumidifiers. The water-coil fresh air dehumidifier (INAD-CW30 and CW50, 300–500 m³/h) is close to a small TFA: it pre-cools outdoor air through a plate exchanger, dries it on a chilled-water coil and passes it back through the exchanger. The rotary model (INAV-HTRW30, 300 m³/h) uses a total heat recovery wheel and its own compressor, so it needs no chilled water.

How InAir checks this at the site survey

  • How many people use each space and for how long, which sets the fresh air quantity.
  • Whether a chilled-water plant exists and has spare capacity, or whether the fresh air needs its own heat pump.
  • Which exhaust air streams (toilets, kitchens, general exhaust) can be brought back past a recovery core.
  • The city's monsoon moisture and summer heat, from InAir's city data, to see whether passive recovery is enough or a coil is needed.
  • Filter grade for the local AQI: MERV-13 standard, HEPA-13 where pollution is heavy.
  • Plant space, duct routes, three-phase power availability and drain points for the coil.

What it costs

InAir RHP heat-pump ERV AHUs start from ₹9.4 lakh for ceiling-mounted models and ₹16.1 lakh for floor-standing models. Ventura ERVs without a coil start from ₹3.8 lakh. These are equipment prices before GST and installation. Fresh air dehumidifiers are quoted after a free site survey. See the price guide for the full list.

Tentative pricing: actual prices may vary based on the site survey.

Common mistakes

  • Calling any fresh air fan a TFA. If it has no coil, it does not treat the air; it only moves it.
  • Sizing the TFA coil on summer heat alone. In most Indian cities the monsoon moisture load is larger.
  • Leaving out the exhaust path. Fresh air pushed in needs a way out, through toilet exhaust or relief air.
  • Fitting a TFA with no recovery where the building throws away thousands of m³/h of cool exhaust air.
  • Choosing filters by habit. The fine filter decides indoor PM2.5, so it should follow the city's air, not the catalogue default.

Sources

  • Bureau of Energy Efficiency, Energy Conservation Building Code 2017 (rev. 2019), §5.3.11 Energy Recovery. lbl.gov copy
  • US Department of Energy, Direct Expansion-Dedicated Outdoor Air Systems: 55 °F dew point rating condition. energy.gov
  • ECMWF / Copernicus ERA5 reanalysis, 2015–2024, analysed by InAir for six cities (as used in our home ventilation guide). in-air.in
  • Bureau of Indian Standards, National Building Code of India 2016, Part 8: fresh air per person; summarised in InAir's NBC and ASHRAE guide
  • InAir RHP heat-pump ERV AHU product page and spec sheets. in-air.in
  • InAir price guide FY 2026–27. pricing.md
Frequently Asked Questions
TFA stands for treated fresh air. A TFA unit is an air handling unit that takes in only outdoor air, filters it and cools and dries it with a chilled-water or DX coil before supplying it to the building.
A TFA is a kind of AHU. A normal AHU mostly recirculates room air with some outdoor air mixed in; a TFA handles 100% outdoor air and exists only to treat the fresh air.
No. A TFA has a cooling coil but usually no energy recovery. An ERV has a recovery core but no coil. A heat-pump ERV, such as InAir's RHP range, has both.
A chilled-water TFA does. A DX TFA or a heat-pump ERV has its own refrigerant circuit, so it suits buildings without a central plant.
ECBC 2017 (§5.3.11) requires heat recovery of at least 50% effectiveness for hotels and hospitals with systems above 2,100 l/s that supply at least 70% outdoor air. Elsewhere it is a design choice.
Rarely. Homes need far smaller airflows, so a ducted or wall-mounted ERV is the usual choice, with a heat-pump ERV or fresh air dehumidifier in very humid cities.
Ready to breathe better? Start with a free site survey.

Our engineers assess your home or building, recommend the right system and the right filter grade for your city, and give you a clear cost estimate. No obligation.