What size exhaust fan do I need? 4, 6, 8, 10 and 12 inch fans explained

The inch number on an exhaust fan is a diameter, not an airflow. Here is what each size carries, and which one your room needs.

Last updated:

Paint booth with large round galvanised exhaust ducts and hoods, showing how duct diameter rises with airflow
exhaust fan size6 inch exhaust fanexhaust fan size for bathroomduct size for exhaust fan4 inch vs 6 inch exhaust fan

An exhaust fan's size, 4, 6, 8, 10 or 12 inches, is a diameter, not an airflow. On a wall or window fan it is the blade sweep; on a duct or inline fan it is the spigot that fits the duct. Most Indian bathrooms need 85–170 m³/h, which a 4–5 inch ducted fan carries over a short run; shower rooms, utility areas and kitchens without a hood need 6–9 inches. The table below gives the size for each room.

Key points

  • Size is a diameter. Indian Standard IS 2312 defines a propeller fan's size as its blade sweep in millimetres. Duct fans are named after the duct they fit.
  • The same size can move very different amounts of air. In IS 2312's own table, a 300 mm (12 inch) fan must deliver at least 1,145 m³/h at the slowest speed listed and 2,520 m³/h at the fastest.
  • Start from the room, not the fan. Work out the airflow from NBC air changes or the ASHRAE minimums, then pick the duct size that carries it.
  • Duct sizes from ASHRAE 62.2: 4 inch up to 85 m³/h, 5 inch up to 170, 6 inch up to 255, 8 inch up to 425, 10 inch up to 765 and 12 inch up to 1359 m³/h, for short rigid runs.
  • Flexible duct carries less: go one size up, and keep it pulled straight.

This page is about sizes. For the full buying checklist (type, noise, motor and duct), see the exhaust fan buying guide.

What does the size of an exhaust fan mean?

A fan's size tells you one dimension. Which dimension depends on the fan.

  • Wall, window and kitchen propeller fans: the size is the blade sweep, the diameter of the circle traced by the blade tips. IS 2312, the Indian Standard for propeller-type AC ventilating fans, says this in so many words: the size of the fan is the blade sweep in millimetres. Its preferred sizes are 200, 300, 380, 450, 600, 900, 1,200 and 1,500 mm.
  • Duct, inline and ceiling fans: the size is the spigot, the round collar the duct slides over. A "6 inch" inline fan fits a 150 mm duct. Sellers often round: 100 mm is sold as 4 inch, 150 mm as 6 inch, 200 mm as 8 inch.
  • Wall cut-out: the hole you make in the wall or glass is set by the fan's frame, not its blades, so it is larger than the sweep. Take it from the maker's drawing before the mason cuts.
Diagram: on a wall propeller fan the size is the blade sweep; on a duct fan it is the spigot diameter that fits the duct
Which diameter the inch number refers to, for the two common kinds of exhaust fan. Tap to enlarge.

None of these numbers is the airflow. Two fans of the same size can differ several times over in how much air they move, because airflow depends on how fast the blades turn, the shape of the blades, and how much resistance the duct, grille, insect mesh and outside cowl put in the way.

Why the same size moves very different airflow

IS 2312 makes the point with its own numbers. It sets a minimum air delivery and a maximum power draw for each size and motor speed. More poles on the motor means a slower fan:

Fan size (blade sweep)Motor polesMinimum air deliveryMaximum power
200 mm (8 in)4435 m³/h38 W
300 mm (12 in)6 / 4 / 21,145 / 1,710 / 2,520 m³/h55 / 90 / 240 W
380 mm (15 in)8 / 6 / 41,735 / 2,000 / 3,250 m³/h77 / 100 / 160 W
450 mm (18 in)8 / 6 / 42,850 / 3,900 / 6,120 m³/h100 / 145 / 410 W

Two things stand out. First, a 300 mm fan can be a 1,145 m³/h fan or a 2,520 m³/h fan, depending on its speed. Second, these are free-air figures: the standard measures delivery with the fan blowing through a short test airway, corrected to free flow. Fit the same fan behind a louvred cowl, an insect mesh or a duct and it delivers less. Small home fans of 4 to 6 inches sit below the standard's smallest preferred size, so for them you depend on the maker's published curve.

The physics of why airflow falls as resistance rises is explained in how an exhaust fan works.

What airflow does each duct size carry?

For ducted fans, the duct sets the limit. ASHRAE Standard 62.2 gives a prescriptive table of the smallest round duct for each fan airflow, for runs of up to 8 m with no more than three bends, with the fan rated at 62.5 Pa (0.25 inch of water). Flexible duct needs to be larger because its ribbed wall adds friction, and the table allows it only up to 400 cfm.

Duct / spigot sizeRigid duct: up toFlexible duct: up toTypical use
4 in (100 mm)85 m³/h85 m³/hSmall toilet, powder room
5 in (125 mm)170 m³/h136 m³/hStandard bathroom, kitchen hood
6 in (150 mm)255 m³/h212 m³/hLarge bathroom, utility area
7 in (180 mm)340 m³/h297 m³/hShower room, small toilet block
8 in (205 mm)425 m³/h425 m³/hLaundry, larger toilet block
9 in (230 mm)595 m³/h595 m³/hEnclosed kitchen without a hood
10 in (255 mm)765 m³/h680 m³/hBasement store, small office pantry
12 in (305 mm)1359 m³/hnot permittedCommercial extract, short run
Bar chart of the largest fan airflow allowed for 4 to 12 inch round ducts, rigid and flexible, per ASHRAE 62.2 Table 5.3
Rigid duct carries more than flexible duct of the same size. Values converted from cfm at 1 cfm = 1.7 m³/h. Tap to enlarge.

Outside those limits, with longer runs, more bends or a filter in the line, the duct must be sized from the fan's curve and the duct's pressure loss. That is design work; the ventilation duct guide explains what goes into it.

Which size for which room?

Here is the method, applied to common Indian rooms. The airflow is the higher of the top of the National Building Code's air-change range for the room and the ASHRAE minimum for that use. The duct size is the smallest that carries it within ASHRAE's short-run limits.

RoomSizeBasisAirflow to plan forRigid ductFlexible duct
Small toilet1.5 × 1.2 × 2.7 mNBC 6–10 ACH; ASHRAE 50 cfm85 m³/h4 in (100 mm)4 in (100 mm)
Standard bathroom2.4 × 1.5 × 2.7 mNBC 6–10 ACH; ASHRAE 50 cfm97 m³/h5 in (125 mm)5 in (125 mm)
Shower room3.0 × 2.0 × 2.8 mNBC 15–20 ACH336 m³/h7 in (180 mm)8 in (205 mm)
Utility / wash area2.5 × 1.8 × 2.8 mNBC 15–20 ACH252 m³/h6 in (150 mm)7 in (180 mm)
Home kitchen with ducted hood3.0 × 2.5 × 2.8 mASHRAE 100 cfm hood; NBC ≥6 ACH170 m³/h5 in (125 mm)6 in (150 mm)
Enclosed kitchen, no hood, wall fan3.0 × 2.5 × 2.8 mASHRAE 300 cfm when in use510 m³/h9 in (230 mm)9 in (230 mm)
Office toilet with 4 WCs4 WCsASHRAE 62.1: 50 cfm per WC340 m³/h7 in (180 mm)8 in (205 mm)
Basement store room6.0 × 4.0 × 2.8 mNBC 3–10 ACH672 m³/h10 in (255 mm)10 in (255 mm)

So a standard bathroom needs about 97 m³/h through a 5 inch duct, and a shower room with a rain shower about 336 m³/h through a 7 inch rigid duct or 8 inch flexible. A home kitchen with a ducted hood needs at least 170 m³/h at the hood; an enclosed kitchen relying on a wall fan needs far more, 510 m³/h while cooking, because a fan on the far wall catches smoke much less well than a hood over the hob. The kitchen exhaust fan size guide goes further on kitchens.

For your own room sizes, the air changes and exhaust fan size calculator does the arithmetic. Bedrooms and living rooms are different: they need fresh air for the people in them, not an exhaust fan. See air changes per hour by room.

When do you need a 10 or 12 inch fan?

Rarely in a flat. Ten and twelve inch fans belong to larger extract jobs: toilet blocks in offices, malls and schools, commercial kitchens, basements and car parks, and plant rooms. Under ASHRAE 62.1, a public toilet needs 50 cfm (85 m³/h) per WC or urinal, so a 10-WC block needs about 850 m³/h, which is already past what a 10 inch duct carries in ASHRAE 62.2's short-run table.

At that scale the fan is chosen on its curve at the system's pressure, and the duct is designed, not picked from a table. InAir's mixed-flow, direct duct and circular duct fans cover ducted extract, and its cabinet centrifugal fans span 1,700 to 120,000 m³/h across 13 models with total pressure up to 1,300 Pa, for central toilet and basement extract.

Wall fan or duct fan: does the size rule change?

A wall or window fan has no duct, so the duct table does not apply. It does still face resistance from its own louvres, any insect mesh, and wind on the outside wall. Because a propeller fan makes little pressure, it loses airflow quickly when anything is in its way. If the room is not on an outside wall, or the duct will be more than a metre or two, use a ducted fan. The inline vs wall exhaust fan comparison covers this choice.

How InAir checks this at the site survey

  • Measures each wet room and notes its use: toilet, shower, utility, kitchen with or without a hood.
  • Sets the airflow from the NBC air changes and ASHRAE minimums, the same basis as the table above.
  • Walks the duct route: length, number of bends, rigid or flexible duct, and where it can leave the building.
  • Checks the outside terminal and any shaft, so the air goes outdoors and not into a ceiling void or a neighbour's window.
  • Checks the door undercut or transfer grille, so replacement air can get in.
  • Selects a fan whose published airflow at the duct's pressure meets the room's need, and measures the airflow at commissioning.

Book it from the contact page; the survey is free.

What it costs

InAir bathroom and toilet exhaust fans, wall and ceiling mounted, start from ₹3,300. Mixed-flow inline fans start from ₹6,600, EC inline duct fans with speed or smart control from ₹15,000, and cabinet centrifugal fans from ₹47,400, before GST and installation. The full list is on the pricing page.

Tentative pricing: actual prices may vary based on the site survey.

Common mistakes

  • Reading "8 inch" as "strong". Size is a diameter; check the airflow at your duct's pressure.
  • Fitting a small fan to a big duct, or a big fan to a small duct. The fan's spigot and the duct should match, and the duct should suit the airflow.
  • Using flexible duct at the rigid-duct size, then letting it sag in the ceiling.
  • Sizing a shower room like a toilet. NBC asks for 15–20 air changes for shower rooms against 6–10 for toilets.
  • Relying on a wall fan in a kitchen instead of a hood over the hob.
  • Cutting the wall opening to the blade sweep, then finding the frame does not fit.

Sources

Frequently Asked Questions
Not necessarily. The size is a diameter: the blade sweep on a wall fan, the spigot on a duct fan. Airflow depends on speed, blade design and duct resistance. Under IS 2312, a 300 mm fan can be rated anywhere from 1,145 to 2,520 m³/h depending on its motor speed.
For a standard Indian bathroom, about 97 m³/h, which a 5 inch (125 mm) rigid duct carries over a short run. A small toilet needs about 85 m³/h on a 4 inch duct. A shower room needs about 336 m³/h on a 7 inch rigid duct.
With a ducted hood over the hob, a 6 inch (150 mm) duct carries up to 255 m³/h over a short rigid run, which covers ASHRAE's 170 m³/h hood minimum. Without a hood, a wall fan needs about 510 m³/h while cooking, which calls for a 9 inch duct size or a larger wall fan.
It is the diameter of the spigot, the round collar the duct fits over. A 4 inch fan fits a 100 mm duct. It says nothing about the airflow, which you should read from the fan's curve at your duct's pressure.
Yes, but go one size up from rigid duct and keep it pulled straight. ASHRAE 62.2 allows less airflow through flexible duct of the same size and does not allow it at all above 400 cfm (about 680 m³/h).
Use the cut-out size on the maker's drawing. It is set by the fan's frame and is larger than the blade sweep or spigot. For a ducted fan, the wall sleeve should match the duct size, with a cowl or louvre that does not choke it.